E45-105 · Signal Interference and EMC · RS485 Temperature-Acquisition Bus · ★★
At the far end of a 30m RS485 bus the device bit-error rate is 2‰, with occasional communication interruptions
[Mechanism] The bus has no termination-matching resistors and the nodes are not isolated, so signal reflections and ground potential differences cause errors at the far end.
[Calculation] With a 30m line, characteristic impedance 120Ω and no 120Ω termination at the far end, the reflection Γ≈1 and signal ringing cause 2‰ bit errors; the 1V ground difference between nodes exceeds the common-mode limit.
[Design Omission] No termination matching, no isolation, no shielded twisted pair.
① Termination matching: add 120Ω matching resistors at both ends of the bus → eliminates reflections, bit errors go to zero
② Shielded twisted pair: run the bus as shielded twisted pair → suppresses crosstalk
③ Node isolation: add signal isolation at each node (≥1.5kV) → cuts the ground potential difference
④ Lower the speed: match the baud rate to the line length (e.g. 9600) → stable edges
⑤ Topology: use a daisy chain, not a star → avoids reflections
⑥ Bias resistors: add pull-up/pull-down bias to guarantee the idle level → guards against noise
⑦ Verify by measurement: bit error rate at full load (≤1e-7) → confirmed
⑧ Institutionalize: write matching and isolation into the communication diagram → gate at the source
GB/T 17626.3-2016 Radiated radio-frequency electromagnetic field immunity test