During capacitor discharge (EDM) in the workshop, the smoke detector gives false alarms (3-4 times per shift)
[Mechanism] EDM discharge sparks radiate a broadband electromagnetic pulse that couples into the smoke detector's weak-signal circuit and makes it misjudge smoke.
[Calculation] With a discharge voltage of ≈100V and MHz-level bandwidth, the field strength E≈several V/m at 1m exceeds the smoke detector's immunity and causes false alarms.
[Design Omission] The smoke-detector cable was not shielded, not filtered and not kept away from the discharge area.
① Shielded twisted pair: change the smoke-detector cable to shielded twisted pair → suppresses radiation
② Move away from the discharge: keep at least 3m from the discharge area or run in metal conduit → reduces field strength
③ RC snubber: add an RC snubber to the discharge circuit → fewer sparks at the source
④ Filtering: add a low-pass filter plus debounce at the signal end → filters the false pulses
⑤ Shield can: mount the detector in a metal enclosure → blocks radiation
⑥ Isolation: isolate the signal → cuts common mode
⑦ Verify by measurement: false alarms under discharge conditions (0 times) → confirmed
⑧ Institutionalize: write smoke-detector EMC into the standard → gate at the source
GB/T 17626.3-2016 Radiated radio-frequency electromagnetic field immunity test