E45-107 · Signal Interference and EMC · Rogowski Coil Current Sensor · ★★
Proximity to a high-current busbar makes the Rogowski coil read +3% high (normally ≤0.5%)
[Mechanism] An external mains-frequency magnetic field penetrates the flexible loop of the Rogowski coil and adds to the measured current's field, shifting the integrated output.
[Calculation] With external field B≈1mT and coil area A, the integral e∝B·A shifts the reading +3%; after shielding B drops.
[Design Omission] The coil was not magnetically shielded, not kept away from high currents, and the leads were not twisted.
① Magnetic shielding: sheathe the coil in permalloy / an iron tube → attenuates the external field by 20dB, shift goes to zero
② Move away from the busbar: keep at least 0.5m from the high current → reduces B
③ Twist the leads: twist the integrator leads as a pair → suppresses magnetic pickup
④ Differential: use two Rogowski coils in a differential arrangement → the common-mode external field cancels
⑤ Shielded twisted pair: shield the signal cable → blocks the electric field
⑥ Calibration: compare against a standard CT on site (difference ≤0.5%) → correct the shift
⑦ Verify by measurement: readings with the busbar at full load (shift ≤0.5%) → confirmed
⑧ Institutionalize: write Rogowski routing into the standard → gate at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields