Knowledge Base › Electrical Sensor Error Case › Absence of TVS Diodes Causes ESD Reset

Absence of TVS Diodes Causes ESD Reset

E45-119 · Signal Interference and EMC · Touch-Panel Display Instrument · ★★

Problem Description

Touching the instrument by hand (ESD) immediately resets/reboots it (several times per shift)

Root Cause

[Mechanism] A human ESD discharge couples through the housing seams into the main board, and the transient high voltage resets the MCU.
[Calculation] With an ESD contact discharge of ±8kV and no TVS, the transient voltage breaks down the I/O and causes a reset; clamping with a TVS to a safe level prevents it.
[Design Omission] No TVS added, housing unshielded, no filtering, wide seams.

Corrective Solution

① Add TVS: fit TVS diodes on the human-machine interface and signal ports (clamp to ±15V) → absorbs ESD, no reset
② Shield the housing: a continuous conductive metal instrument housing → Faraday cage
③ Treat the seams: add conductive gaskets/spring fingers at the seams → less coupling
④ Filtering: add RC filtering on the I/O → filters the spikes
⑤ Isolation: add isolation to the interfaces → cuts coupling
⑥ Grounding: connect the housing directly to protective earth → provides a discharge path
⑦ Verify by measurement: ESD gun at ±8kV discharge (no reset) → confirmed
⑧ Institutionalize: write ESD protection into the standard → gate at the source

Checklist

Reference

GB/T 17626.2-2018 Electrostatic discharge immunity test