MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Electrical Sensor Error Case › Switching-Supply High-Frequency Noise Coupling Into the Analog Signal

Switching-Supply High-Frequency Noise Coupling Into the Analog Signal

E45-131 · Power Supply · Analog Input Module · ★

Problem Description

The 4-20mA channels of the analog input card carry ±0.3% random noise, and the FFT shows a 100kHz spike matching the switching-supply frequency

Root Cause

[Mechanism] The switching supply runs at 100kHz; transformer leakage inductance and output-diode reverse recovery generate high-frequency common-mode noise that couples through the Y capacitor and parasitic capacitance onto the analog shield and signal ground, adding acquisition noise.
[Calculation] With a switching frequency fs=100kHz the coupling impedance through the shield-to-ground capacitance Cg=100pF is Z=1/(2πfC)=1.6kΩ; a common-mode voltage Vcm=1V drives 0.6mA of noise current into ground, producing ±0.3% reading fluctuation across the signal-ground resistance.
[Design Omission] The analog supply was not separated from the digital and power supplies: they shared one switching supply, the shield was grounded at both ends forming a ground loop that amplified the noise, and neither a linear supply nor a common-mode choke was used.

Corrective Solution

① Independent linear supply for the analog section: use a series-regulated linear supply for sensing (no high-frequency switching) → no 100kHz noise at the source
② Common-mode choke: insert a common-mode inductor (100mH) in the sensor supply → chokes the high-frequency common-mode noise
③ Single-point shield grounding: ground only at the signal-source end to break the ground loop → no ground-loop common mode
④ Optimize the supply Y capacitor: choose a low-leakage transformer plus a small Y capacitor → less common-mode coupling
⑤ Separate analog and digital grounds: join at one point → digital noise does not leak into the analog section
⑥ FFT noise measurement: confirm the 100kHz spike is gone → data verification
⑦ Shielded twisted-pair signal cable: bond the shield to the chassis → better common-mode immunity
⑧ Write the supply partitioning into the electrical drawing → gate at the source

Checklist

Reference

GB/T 17626.6-2017

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL