E45-132 · Power Supply · Dual Redundant 24V Supply · ★
When the main supply switches to the standby, transmitters lose power for 0.3s; the PLC analog inputs zero out briefly and trigger a false shutdown
[Mechanism] A relay-based changeover between the two supplies has a dead time (from release to pickup); during the dead time the load briefly loses power, and if the capacitor energy is insufficient the voltage drops and the equipment resets.
[Calculation] With a changeover dead time t=0.3s and a load current I=0.3A, holding the voltage ≥18V needs a hold-up capacitor C≥I×Δt/ΔU=0.3×0.3/(24−18)=15mF; the original design had none → momentary power loss.
[Design Omission] The redundant changeover was not seamless: a mechanical relay left a dead time, no hold-up capacitor was added and no 0ms-changeover module was chosen, and the PLC applied no filtering to the brief zeroing.
① Uninterruptible changeover module: use ORing diodes or a 0ms-changeover supply module → no dead time, no power loss
② Hold-up capacitor: add 15mF or more of electrolytic capacitance across the bus → covers the 0.3s changeover
③ Solid-state changeover instead of a relay: solid-state switching <1ms → the dead time is negligible
④ PLC debounce filtering: hold the last analog value through a 100ms dropout → no false shutdown
⑤ Parallel the two supplies through ORing diodes: if either one drops, the other keeps supplying
⑥ Measure the changeover voltage dip: U ≥18V during changeover → confirmed no power loss
⑦ Standby auto-transfer test: simulate a main-supply failure and verify no interruption → confirmed by measurement
⑧ Make seamless changeover a mandatory item in the power design → gate at the source
GB/T 7260.3-2003