Knowledge Base › Electrical Sensor Error Case › Power and Signal Grounds Not Separated Causing Common-Mode Interference

Power and Signal Grounds Not Separated Causing Common-Mode Interference

E45-133 · Power Supply · Thermocouple Acquisition Card · ★

Problem Description

The temperature sensor reading jumps ±1.5℃ as large shop-floor equipment starts and stops, with obvious 50Hz line-frequency pickup

Root Cause

[Mechanism] A potential difference exists between the supply system ground and the signal ground (earth) because of three-phase imbalance and leakage currents; once the two systems are tied together, that difference becomes a common-mode voltage that couples into the signal, and since the acquisition card's CMRR is finite the common mode converts to differential mode and the reading jumps.
[Calculation] The measured ground potential difference is Vg=2V (50Hz) and the card CMRR=90dB, so the converted differential voltage Vd=Vg/10^(90/20)=63μV, about 0.1℃; the measured ±1.5℃ means grounding the shield at both ends formed a ground loop that amplified Vg by tens of times.
[Design Omission] There was no single-point grounding: the supply and signal grounds were joined at several points to form a ground loop, the shield was grounded at both ends bringing in a large loop current, and no isolated acquisition was used to break the common mode.

Corrective Solution

① Single-point grounding: join the signal and power grounds at just one point in the cabinet → breaks the ground loop and eliminates the loop current
② Isolated acquisition card: optocoupler-isolated input (≥1kV) → cuts the coupling of the ground potential difference
③ Single-ended shield grounding: earth the shield at the source end only → no ground loop
④ Equipotential bonding: bring equipment frames, shields, and ground bars to the same potential → the common mode stays uniform and does not convert to differential
⑤ Higher-CMRR card: CMRR ≥120dB → for the same Vg the converted differential voltage drops another 30×
⑥ Ground-potential measurement: equipment-to-equipment ground voltage ≤1V → confirmed no large loop current
⑦ Re-test with large equipment starting and stopping: reading jump ≤0.2℃ → confirms the isolation works
⑧ Write the separated grounding system on the drawing → gate at the source

Checklist

Reference

GB/T 18268.1-2010