E45-186 · Grounding and Shielding · Servo Feedback Shielded Cable · ★★
After the triple-shielded servo cable was grounded at a common end, the encoder still skips counts from VFD interference
[Mechanism] A triple shield (overall shield + individual shields + braid) must be grounded in layers: the individual shields bond to signal ground at one end to suppress crosstalk between wires, and the overall shield bonds to PE to suppress external fields; if all are mixed to one end, the individual shields lose their pair isolation and the overall shield no longer suppresses external fields.
[Calculation] Leaving the individual shields ungrounded raises the inter-pair crosstalk coupling by 20dB; bonding the overall shield to signal ground instead of PE means the external-field coupling e=2πfBA is not carried away.
[Design Omission] No layered grounding was done; all three shields are terminated at the same point.
① Individual shields to SG at one end: bond each twisted-pair shield to signal ground at the drive end → suppresses crosstalk between wires
② Overall shield to PE: bond the overall shield to the chassis PE → suppresses external fields
③ Layers unmixed: do not short the individual shields to the overall shield → each keeps its role
④ 360° clamping: terminate each shield separately all around at the connector → low resistance
⑤ Isolated drive: use a differential isolated encoder output → common mode cannot couple through
⑥ Noise test: with the VFD at full load, encoder jitter <±1 pulse → verify
⑦ Crosstalk ratio: inter-pair crosstalk ratio >40dB → verify isolation
⑧ Write layered grounding into the cable specification → gate at the source
GB/T 20909-2007 Control cables for use with frequency converters