E45-188 · Grounding and Shielding · Differential Pressure Transmitter · ★★
The transmitter output clips and distorts the instant the motor starts; the common-mode voltage measures 15V, beyond the ±7V range
[Mechanism] A differential input tolerates only a limited common-mode voltage; beyond that range the front-end amplifier saturates or the protection diodes conduct and the normal differential signal is clipped; the common mode comes from the ground potential difference accumulating along the long line.
[Calculation] Ground potential difference Ucm=15V against an interface common-mode limit of ±7V → 8V over; the internal op-amp output is clamped to the supply rail and the differential signal distorts.
[Design Omission] Neither a high-common-mode-range interface was selected nor was the common mode isolated.
① High common-mode interface: select a differential input with a common-mode range ≥±25V → tolerates the ground difference
② Isolated front end: add an isolation amplifier (1500V isolation) → common mode cannot couple through
③ Single-ended to differential: transmit the signal differentially → little common-to-differential conversion
④ Equipotential to lower the difference: bond the PE of both devices to keep Ucm<2V → tackles the root
⑤ Single-end shielding: bond the shield at one end → introduces no extra common mode
⑥ Range test: measure the actual Ucm<the interface range → verify
⑦ Distortion ratio: no clipping in the output when the motor starts or stops → verify
⑧ Write the common-mode requirement into interface selection → gate at the source
GB/T 30114.1-2014 Industrial process measurement