Knowledge Base › Electrical Sensor Error Case › No Isolation Between Chassis and Internal Circuit, Breakdown

No Isolation Between Chassis and Internal Circuit, Breakdown

E45-189 · Grounding and Shielding · Integrated Temperature Transmitter · ★★

Problem Description

In a humid environment the transmitter's insulation degrades, the chassis becomes live, and the output jumps erratically

Root Cause

[Mechanism] The chassis (bonded to PE) and the internal circuit ground are not isolated or are under-insulated; humidity lowers the leakage resistance between chassis and circuit, so interference and leakage on PE enter the circuit directly; chassis potential fluctuations couple to the signal through stray capacitance.
[Calculation] Normal insulation resistance >100MΩ drops to 1MΩ after damp; 1V of noise on PE divides down to millivolt-level interference at the signal terminals.
[Design Omission] The circuit ground and chassis rely only on thin insulation, with no reinforced isolation or creepage distance.

Corrective Solution

① Reinforced isolation: use ≥2.5kV insulation spacing between the circuit ground and chassis → no cross-coupling
② Creepage distance: leave creepage ≥8mm on the PCB according to the pollution degree → prevents damp breakdown
③ Conformal coating: apply conformal coating to the board → moisture-proof insulation
④ Chassis to PE: bond the chassis reliably to PE → fixed chassis potential
⑤ Signal isolation: add isolation to the output (1500V) → decouples chassis and circuit
⑥ Insulation test: measure chassis-to-circuit insulation >100MΩ → verify
⑦ Damp-heat test: output is stable after the humidity chamber run → verify
⑧ Write the isolation requirement into the structural design → gate at the source

Checklist

Reference

GB/T 4208-2017 Degrees of protection provided by enclosures (IP Code)