E45-190 · Grounding and Shielding · Strain Gauge Measurement Cable · ★
The strain measurement has more noise than before; the shield is found connected to signal ground instead of PE
[Mechanism] The shield should be bonded to the low-impedance PE as an electrostatic-shielding reference; wrongly connected to signal ground (SG), it radiates the circuit noise on SG outward and couples it back, and the shield also picks up and amplifies SG's own noise.
[Calculation] SG noise of 0.5V couples through the shield capacitance C=50pF to the adjacent signal line → an induced ΔU≈5mV, larger than without any shield.
[Design Omission] The installer confused SG with PE and miswired the shield to signal ground.
① Rewire to PE: reconnect the shield to the chassis PE (low impedance) → provides the correct shielding reference
② Labeling: mark the SG and PE terminals with color codes (blue / yellow-green) → prevents miswiring
③ Single-end grounding: bond the shield to PE at the receiving end only → no circulating current
④ Twisted pair: use twisted pair for the signal → little common-to-differential conversion
⑤ Independent SG: keep the signal ground floating and bond it to PE at one point → not contaminated by shield noise
⑥ Noise test: after rewiring, the peak-to-peak noise drops >50% → verify
⑦ Wiring check: check each shield grounding terminal point by point → prevents miswiring
⑧ Write the wiring-diagram annotations into the work card → gate at the source
GB/T 13992-2010 Metallic bonded resistance strain gauges