Ground Grid Potential Difference Causes Measurement Drift

E45-191 · Grounding and Shielding · Remote Pressure Sensor · ★★

Problem Description

A remote sensor 200m from the master control drifts ±0.3% over the day/night cycle as the plant load changes

Root Cause

[Mechanism] In a large plant the load current produces ground potential differences between the many grounding electrodes; the remote sensor ground and the master control ground are unequal, and that difference becomes a common-mode signal through the signal return, adding to the measured value and fluctuating with the load cycle.
[Calculation] Ground grid current I=50A across an inter-electrode resistance of 0.02Ω → potential difference U=1V; combined with a 100Ω source impedance it works out to ≈0.2% drift on the 4-20mA signal, matching the ±0.3%.
[Design Omission] The remote unit and the master control were neither equipotentially bonded nor isolated.

Corrective Solution

① Equipotential bonding: bond the remote cabinet to the master control with ≥25mm² copper cable → Ucm<0.5V
② Signal isolation: add isolation to the sensor output (1500V) → common mode cannot couple through
③ Star grounding: bring both grounds to the same grounding electrode → unified reference
④ Single-end shielding: bond the long-line shield to PE at one end only → no circulating current
⑤ Common-mode range: interface common mode ≥±15V → margin
⑥ Drift test: reading changes <0.1% between load peak and valley → verify
⑦ Potential-difference test: measure Ucm<0.5V between the two grounds → verify equipotential
⑧ Write remote grounding into the plant grounding diagram → gate at the source