E45-211 · Grounding and Shielding · Field Sensor Connector · ★
The shielded cable was grounded at the connector with just a single wire strand; high frequencies still coupled in and the shielding effectiveness was low
[Mechanism] The shield should be ring-crimped 360° to the shell at the connector; a single strand leaves the shield discontinuous at the port, creating a slot that leaks high-frequency fields and giving high contact impedance.
[Calculation] A single strand gives a contact impedance ≈0.5Ω versus <0.01Ω for a 360° ring crimp, a 50-fold difference; the port slot leaks fields >100MHz and drops the SE by 20dB.
[Design Omission] The installer hand-soldered a single strand instead of ring-crimping, so the shield was broken at the port.
① 360° ring crimp: use a shielding ring-crimp tool to bond the shield all round to the shell → continuous
② Shield adapter ring: add a shield adapter ring at the connector → low impedance
③ Backshell clamp: clamp the cable backshell onto the shield → no loosening
④ Contact test: port contact impedance <0.01Ω → confirmed
⑤ RF test: measure port SE >60dB → no leakage confirmed
⑥ Strand check: no broken or loose shield strands → confirmed
⑦ Process card: write the ring-crimp process into the assembly card → prevents recurrence
⑧ Write the termination rule into connector assembly → control at the source
GB/T 11313.1-2013 Radio-frequency connectors