E45-212 · Grounding and Shielding · Substation Grounding Grid · ★★
During a switching overvoltage a far higher-than-expected spike appeared at the signal cable port and damaged the module
[Mechanism] The grounding grid and its leads have distributed inductance and capacitance that form an LC resonance near the system's switching frequency; the transient overvoltage is amplified in the grounding system and strikes back at the equipment port through the cable shield.
[Calculation] With grid L≈10μH and C≈1μF the resonance is f≈1.6kHz; when the switching wave contains that component it is amplified and the port spike rises from 2kV to 6kV.
[Design Omission] The grounding-system resonance was not evaluated and the port had no adequate SPD.
① Damping resistor: insert a small damping resistor between the grounding lead and the grid → damps the resonance
② Multi-stage SPD: fit multi-stage SPDs at the port (residual voltage ≤ equipment withstand) → clamps the surge
③ Frequency avoidance: choose the lead length so the resonance avoids the dominant switching frequency → no amplification
④ Equipotential bonding: bond the equipment tightly to the grounding grid → less strike-back
⑤ Shielded conduit: run the signal cable in a metal conduit earthed nearby → diverts the current
⑥ Residual-voltage test: SPD residual voltage ≤ port withstand → confirmed
⑦ Spike recording: record the switching-overvoltage waveform and confirm no amplification → confirmed
⑧ Write the resonance evaluation into the grounding design → control at the source
GB 50057-2010 Design code for protection of structures against lightning