E45-213 · Grounding and Shielding · Two-Wire Transmitter · ★★
The negative terminal (signal-) of a two-wire transmitter accidentally touched the enclosure (PE) and shorted, driving the measurement to a constant full-scale reading
[Mechanism] In a two-wire transmitter the signal- and supply- share a terminal and should float, developing the signal across the load; if signal- touches the enclosure (PE), the PE short-circuits and diverts the signal loop, the voltage across the load becomes abnormal and the reading goes full scale or wrong.
[Calculation] With signal- touching the enclosure through R=0.1Ω, the 24V supply feeds the load (250Ω) and the PE short-circuit branch in parallel; the load current is diverted, the voltage drop becomes abnormal and the reading goes full scale.
[Design Omission] During wiring the signal- touched the shield/enclosure and no insulation was provided.
① Insulation: keep the insulation between signal- and the enclosure >100MΩ → no short
② Floating supply: keep the two-wire supply loop floating with a single reference point → no enclosure contact
③ Shield off the signal: bond the shield to PE, not to signal- → prevents accidental short
④ Wiring check: verify wire by wire that signal- does not touch the enclosure → prevents mistakes
⑤ Short test: on power-up measure signal--to-enclosure insulation >100MΩ → confirmed
⑥ Full-scale check: no full-scale reading → confirmed
⑦ Terminal insulation: fit insulating sleeves on the signal terminals → prevents contact
⑧ Write the wiring rule into the terminal-block drawing → control at the source
GB/T 17614.1-2008 Transmitters for use in industrial-process control systems