E45-214 · Grounding and Shielding · Differential-Input Instrument · ★★
The instrument was rated CMRR>100dB, but in practice it rejected common-mode noise by only 20dB and the reading was disturbed by mains frequency
[Mechanism] A high CMRR depends on the two inputs being symmetrical (impedance-balanced); if improper grounding makes one end unbalanced (for example, one end to PE and one floating), the common-mode-to-differential conversion factor increases and the actual CMRR collapses.
[Calculation] With a 1kΩ difference in the two inputs' ground impedance and a common-mode impedance of 10kΩ, the imbalance is 10% and the CMRR drops from 100dB by about 20dB.
[Design Omission] In an attempt to fight interference, one side of the differential input was grounded, destroying the symmetry.
① Keep symmetry: make both differential ends' ground impedance equal, do not ground one side → preserves CMRR
② Floating differential: keep the differential input floating and isolated → symmetry intact
③ Isolation front end: add an isolation amplifier → no common-mode coupling
④ Equipotential bonding: bond the PE of the equipment at both ends → small common mode
⑤ Single-end shield: bond the shield to PE at one end only → no imbalance introduced
⑥ CMRR test: measure actual CMRR >90dB → recovery confirmed
⑦ Impedance balance: measure the ground-impedance difference between the two ends <1% → symmetry confirmed
⑧ Write grounding symmetry into the differential interface design → control at the source
GB/T 30114.1-2014 Industrial process measurement