E45-221 · Grounding and Shielding · Equipotential Bonding of a Large Cabinet Group · ★★
Between the cabinets equipotential bonding coexisted with separate PE connections, forming a network within a network and causing low-frequency circulating current
[Mechanism] When equipotential bonding coexists with separate PE connections, the two paths form a closed parallel network; the ground-potential difference drives a circulating current between them and re-introduces common-mode interference.
[Calculation] With 0.05Ω in each path and a ground-potential difference ΔU=1V, the circulating current I=10A and the resulting voltage drop pollutes the equipment ground.
[Design Omission] Equipotential bonding and multi-point PE grounding were not coordinated, forming a redundant closed loop.
① Unified topology: use star equipotential bonding for the cabinet group (one point to PE) → no closed loop
② Remove the redundancy: keep the equipotential bar and disconnect each cabinet's separate PE → breaks the loop
③ Single-point PE: bond the equipotential bar to the ground grid at one point only → one reference
④ Loop test: measure the equipotential network's circulating current ≈0 → confirmed
⑤ Potential difference: ΔU between cabinets <0.5V → confirmed
⑥ Isolation: add signal isolators → no common-mode coupling
⑦ Topology diagram: draw the grounding topology and review it for loops → confirmed
⑧ Write the topology principle into the grounding design → control at the source
GB/T 2887-2011 General specification for computer field