E45-222 · Grounding and Shielding · Long Outdoor Shielded Cable · ★★★
On a lightning strike a shielded cable grounded at both ends induced a large current that burned through its ends and damaged the equipment
[Mechanism] For a long outdoor cable whose shield is grounded at both ends, the changing magnetic field of a lightning strike induces a longitudinal EMF around the shield loop; the two grounds close the loop, a large induced current flows, burns through the ends and strikes back at the equipment.
[Calculation] Using the lightning field rate dB/dt and the loop area A, the induced e=∮(dB/dt)·dA; typically several hundred volts and tens of amperes burn the cable ends, whereas single-end grounding leaves the loop open with no current.
[Design Omission] The long outdoor cable shield was grounded at both ends with no SPD fitted.
① Single-end grounding: ground the long outdoor cable shield at one end only → open loop, no induced current
② Capacitor at the far end: where both ends must be grounded, use a 10nF capacitor → passes RF, blocks the lightning field
③ Fit SPDs: install signal SPDs at both ends (residual voltage ≤ equipment withstand) → clamps the surge
④ Equipotential bonding: bond the equipment at both ends to equal potential → small ΔU
⑤ Continuous shield: keep the shield unbroken → even current drainage
⑥ Residual-voltage test: SPD residual voltage ≤ port withstand → confirmed
⑦ Induction test: simulate a strike and measure the end current ≈0 → confirmed
⑧ Write outdoor grounding into the lightning-protection design → control at the source
GB 50057-2010 Design code for protection of structures against lightning