E45-244 · Wiring and Terminals · Wiring After Maintenance · ★
After maintenance the wires were removed without recording their numbers; on reassembly they were put on the wrong terminals and the flow reading came out reversed
[Mechanism] The removed wires were neither marked nor recorded, so reassembly from memory put them in the wrong places; signal wires reversed or mis-crossed, the instrument reading no longer matched reality, and with no teardown record it was hard to trace.
[Calculation] Cross-connecting the signal wires corrupted the range mapping and gave a reversed error of 100%; the flow, which was positive, displayed negative and caused a wrong control action.
[Design Omission] No tagging of removed wires, no photographic record, and no reassembly verification process.
① Tags: hang a number tag on each wire before removal → no mix-up
② Photograph: photograph the wiring before removal → traceable
③ Core sleeves: fit a numbered sleeve on every core → clear
④ Reassembly check: restore core by core per the drawing → accurate
⑤ Two-person verification: have two people check after reassembly → no mistakes
⑥ Trial reading: after reassembly check the reading is close to reality → confirmation
⑦ Documentation: file the wiring diagram → keep a record
⑧ Write the wire-removal rules into maintenance → control at the source
GB/T 3797-2016 Electrical control equipment