Uneven Voltage Drop Across Cascaded Terminal Blocks

E45-245 · Wiring and Terminals · Distributed IO · ★

Problem Description

On a long terminal strip the last module was fed 1.5V below the first; the analog input reading at the far end ran low

Root Cause

[Mechanism] Several modules drew power in series from the same terminal strip; the accumulated conductor resistance along the strip increases the voltage drop at the far end, and the module there runs at too low a voltage and enters its nonlinear region.
[Calculation] Strip resistance 0.01Ω/cm×50cm=0.5Ω; with a total current of 5A the far-end drop is 2.5V, taking the module from 24V down to 21.5V, close to the undervoltage threshold.
[Design Omission] No zoned power supply, no evaluation of the strip's voltage drop, and no power feed at the far end.

Corrective Solution

① Zoned supply: feed each zone independently → even voltage
② Strip-drop check: verify the strip drop <0.5V → no bias
③ Far-end feed: add a feed point at the far end → raise the voltage
④ Voltage measurement: measure ≥23V at the far end → confirmation
⑤ Larger busbar: use a larger cross-section busbar → lower resistance
⑥ Redundant feed: feed from both ends → stable
⑦ Undervoltage alarm: alarm when the voltage <22V → early warning
⑧ Write the power distribution into the drawing → control at the source

Checklist

Reference

GB/T 3797-2016 Electrical control equipment

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »