E45-246 · Wiring and Terminals · Control-Cabinet Harness · ★
The duct was packed with wires; the cabinet temperature ran 12℃ above design and the terminals aged faster
[Mechanism] Too high a duct fill blocks air circulation, the heat from the wires cannot escape, heat builds up inside and around the duct, and the long-term high temperature around nearby terminals and relays accelerates insulation aging.
[Calculation] Above a 60% fill the heat-dissipating area is insufficient and the temperature rise inside the duct climbs from 15K to 35K; by the 10℃ halving rule the insulation life is cut to one quarter.
[Design Omission] The fill ratio was not controlled, no space for heat dissipation, and no current/temperature-rise evaluation.
① Fill control: keep the duct fill ≤40% → dissipate heat
② Separate ducts: run power and low-level circuits in separate ducts → less heat
③ Ventilation space: leave space above the duct → convection
④ Temperature measurement: cabinet rise <25K → confirmation
⑤ Wire sizing: choose one gauge larger than the current requires → no heating
⑥ Add fans: fit fans at hot spots → forced cooling
⑦ Aging inspection: check the insulation periodically → early prevention
⑧ Write the fill ratio into the wiring spec → control at the source
GB/T 3797-2016 Electrical control equipment