E45-248 · Wiring and Terminals · High-Current Sensor · ★
The CT secondary terminal ran hot for a long time; the insulation carbonized and short-circuited
[Mechanism] A poor contact or excessive load on the CT secondary terminal keeps the contact point hot; the insulation carbonizes and forms a conductive path, finally shorting turn-to-turn or to ground, and the CT saturates and distorts.
[Calculation] A contact resistance of 0.1Ω at 5A dissipates 2.5W and the temperature rise exceeds 60℃; the long-term overtemperature carbonizes the insulation until its resistance falls to the kΩ level and shorts.
[Design Omission] The CT load was not evaluated, the terminal was not tightened, and the temperature was not measured.
① Load check: keep the CT load ≤rating → no saturation
② Tighten the terminal: meet the torque specification → no heating
③ Temperature measurement: check the terminal rise <40K → confirmation
④ Insulation measurement: measure >10MΩ → no carbonization
⑤ Infrared survey: measure the temperature with an IR camera → early warning
⑥ Shorting for safety: short the secondary before taking the CT out of service → safe
⑦ Aging inspection: check periodically for carbonization → replace early
⑧ Write the load evaluation into the drawing → control at the source
GB/T 20840.2-2014 Instrument transformers - Part 2: Additional requirements for current transformers