E45-250 · Wiring and Terminals · Post-Modification System · ★
After the equipment modification the wiring was not updated on the drawing, and the new sensor was tied into the wrong circuit
[Mechanism] The modification work did not update the wiring diagram at the same time; the new measuring point was connected to the wrong terminal per the old drawing, so the signal entered an unmatched acquisition channel, making the readings meaningless and cross-talking.
[Calculation] The signal was wrongly connected to a millivolt channel although it was designed for 4-20mA; the wrong range mapping made the reading 500% of rating and trigger an over-range.
[Design Omission] Drawing and construction were out of step, there was no change-closure loop, and no circuit verification.
① As-built matching: update the drawing together with the change → consistent
② Circuit verification: check that each point's signal matches the drawing symbol → confirmation
③ Change closure: always issue a change order for modifications → records
④ Channel matching: match the signal type to the channel → no mistake
⑤ Two-person verification: have two people check critical points → no mistakes
⑥ Trial reading: read each point and check it is close to reality → confirmation
⑦ Archiving: archive drawing and as-built records → traceable
⑧ Write the drawing/reality match into management → control at the source
GB/T 3797-2016 Electrical control equipment