E45-256 · Wiring and Terminals · High-Voltage-Side Terminal · ★
The VFD output terminal tracked to the enclosure and tripped the overcurrent protection
[Mechanism] The insulation distance from the terminal to the enclosure was insufficient, or the surface was contaminated and damp; the high-voltage transient produced surface tracking that formed a short-to-ground path, and the VFD tripped on overcurrent.
[Calculation] A 690V output needs a creepage distance ≥12mm but only 8mm was installed; the contamination layer raises the surface conductance and the leakage current reaches the ampere level, tripping the protection.
[Design Omission] The high-voltage creepage was not checked, no cleaning, and no distance margin.
① Sufficient creepage: provide ≥12mm creepage for the voltage → no tracking
② Covers: fit dust covers on the terminals → prevent buildup
③ Insulation measurement: measure to ground >10MΩ → confirmation
④ Clearance: keep the distance to the enclosure at or above the specified value → no breakdown
⑤ Coating: apply conformal coating → keep out moisture
⑥ Overcurrent protection: set the protection value sensibly → no nuisance trips
⑦ Contamination inspection: clean periodically → early prevention
⑧ Write the creepage requirement into selection → control at the source
GB/T 12668.3-2012 Adjustable speed electrical power drive systems - Part 3: EMC requirements and specific test methods