E45-257 · Wiring and Terminals · Analog Shielding · ★
The shield drain was led out too long instead of being bonded to the enclosure; it picked up high-frequency noise and made the readings spike
[Mechanism] An overlong shield ground lead forms a floating antenna; high-frequency interference is inductively coupled through the long lead into the signal circuit, so the shield turns from protection into a noise source.
[Calculation] A 100mm lead has an inductive reactance ωL≈60Ω at 100MHz; the induced noise voltage adds to the signal and makes the analog input spike by ±0.3%.
[Design Omission] No 360° ring clamp, an overlong ground lead, and no bonding to the enclosure.
① 360° ring clamp: use a ring-clamp gland for the shield → fully enclosing
② Short lead: keep the ground lead <20mm → no pickup
③ Bond to enclosure: bond to the enclosure locally → low impedance
④ High-frequency test: check for no spikes → confirmation
⑤ Shielding effectiveness: verify ≥60dB → confirmation
⑥ Short routing: keep the shielded section as short as possible → less coupling
⑦ Noise sweep: sweep the frequency and watch the noise → early warning
⑧ Write shield grounding into the process → control at the source
GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields