Knowledge Base › Electrical Sensor Error Case › Condensation Inside the Junction Box

Condensation Inside the Junction Box

E45-258 · Wiring and Terminals · Site with Large Temperature Swings · ★

Problem Description

Large day-night temperature swings caused condensation on the inner wall of the junction box; leakage between terminals drifted the signal

Root Cause

[Mechanism] Moisture in the air inside the box condenses on the cold wall; a water film forms on the terminals and wires, the insulation resistance drops, leakage current appears, and the signal is shunted and drifts.
[Calculation] Once the dew point is reached the water film drops the insulation from >100MΩ to <1MΩ; the leakage current produces a ±1% drift across the signal-source impedance.
[Design Omission] No breather valve, no heating, and no sealed dry enclosure.

Corrective Solution

① Breather valve: fit an explosion-proof breather valve → equalize
② Heating tape: add a heat-tracing tape in cold weather → no condensation
③ Desiccant: put desiccant inside → absorb moisture
④ Good sealing: seal the box → keep out damp
⑤ Insulation measurement: measure >10MΩ → confirmation
⑥ Dew-point check: evaluate the dew point → avoid condensation
⑦ Condensation inspection: check for no droplets → early prevention
⑧ Write the anti-condensation requirement into installation → control at the source

Checklist

Reference

GB 4208-2017 Degrees of protection provided by enclosures (IP code)

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »