Knowledge Base › Electrical Sensor Error Case › Long-Term Drift Not Re-Calibrated

Long-Term Drift Not Re-Calibrated

E45-280 · Calibration · Load Cell · ★

Problem Description

One year after commissioning without re-calibration, the zero drift accumulated to 0.8%FS and the batching error grew steadily

Root Cause

[Mechanism] Creep of the elastic body and aging of the bridge slowly drift the zero and sensitivity; without long-term calibration the error accumulates beyond the tolerance and the measurement reference keeps shifting.
[Calculation] Drift of 0.8%FS per year, an average of 0.067%FS per month, crosses the 0.4%FS alarm line within half a year and reaches 0.8% in a year.
[Design Omission] No calibration interval was set and no automatic drift monitoring was provided.

Corrective Solution

① Fixed interval: re-calibrate once every six months → drift under control
② Drift monitoring: monitor the zero change in real time → alarm above 0.4%
③ Self-calibration: automatic zeroing at no load → remove daily drift
④ Trend analysis: record the drift curve → predict replacement
⑤ Recheck: compare against an actual weigh after calibration → verification
⑥ Overdue ban: warn and stop production when overdue → prevent out-of-tolerance
⑦ Aging management: replace at end of life → no accumulation
⑧ Write the interval into the log → control at the source

Checklist

Reference

JJG 669-2003 Verification Regulation of Load Cells

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »