E45-284 · Calibration · Temperature Transmitter · ★
Only the zero was calibrated, not the full scale; the full-scale reading ran low by 6% and temperature control went out of tolerance
[Mechanism] Calibrating only the zero leaves the slope uncorrected, so the full-scale end point deviates from the true value and the ratio extrapolated from the single zero point is inaccurate at the high end.
[Calculation] The zero is accurate but the full-scale point actually reads low by 6%; linear extrapolation makes the high end off by 6%FS across the range.
[Design Omission] No full-scale calibration was done and the slope was not set from two points.
① Two-point calibration: calibrate the zero and full scale together → accurate slope
② Full-scale verification: measure the full scale after calibration → verify the high end
③ Slope check: check that the slope is close to 1 → no deviation
④ Recheck: compare the mid-points → accurate over the whole range
⑤ Out-of-tolerance alarm: alarm when the full-scale error >1% → early warning
⑥ Periodic calibration: calibrate every quarter → prevent drift
⑦ Records: keep the two-point data on file → traceability
⑧ Write the two-point requirement into the procedure → control at the source
GB/T 17614.1-2015 Industrial process control systems - Transmitters - Part 1: Methods of evaluating the performance