Knowledge Base › Electrical Sensor Error Case › Zero Drift Not Tracked

Zero Drift Not Tracked

E45-285 · Calibration · Flow Transmitter · ★

Problem Description

During long-term operation the zero slowly drifted up by 0.5%FS; with no automatic tracking the cumulative measurement read high

Root Cause

[Mechanism] Electronic zero drift and medium buildup gradually shift the zero; with zero tracking off or its period too long, the steadily drifting reference is never corrected.
[Calculation] Drift of 0.1%FS per month reaches 0.6%FS in half a year, exceeding the tolerance; the cumulative flow error is scaled by 0.6%.
[Design Omission] No automatic zero tracking was set and no periodic zeroing was done.

Corrective Solution

① Automatic tracking: enable automatic zero tracking → remove daily drift
② Periodic zeroing: zero at no load every shift → correct reference
③ Drift monitoring: alarm when the zero change exceeds 0.3% → early warning
④ Trend analysis: record the drift curve → predict replacement
⑤ Recheck: compare with the actual flow after calibration → verification
⑥ Out-of-tolerance ban: warn when out of tolerance → prevent misuse
⑦ Aging management: replace at end of life → no accumulation
⑧ Write tracking into the procedure → control at the source

Checklist

Reference

GB/T 17614.1-2015 Industrial process control systems - Transmitters - Part 1: Methods of evaluating the performance