E45-286 · Calibration · Pressure Sensor · ★
Not calibrated for two years, the error accumulated from 0.5%FS to 3%FS and the safety-valve setting became inaccurate
[Mechanism] Going past the due date without calibration leaves drift and aging errors uncorrected; they exceed the tolerance and the measurement loses a trustworthy reference.
[Calculation] Drift of 1.2%FS per year reaches 2.4%FS in two years; adding the original 0.5% gives 3%FS, exceeding the 1% limit.
[Design Omission] No calibration interval was set and there was no due-date reminder.
① Fixed interval: calibrate once a year → drift under control
② Due-date alarm: remind as the date approaches → no missed calibration
③ Overdue ban: warn and stop production when overdue → prevent out-of-tolerance
④ Drift monitoring: monitor in real time → alarm above 0.5%
⑤ Recheck: compare with the actual flow after calibration → verification
⑥ Log: keep a calibration log → manage the intervals
⑦ Aging management: replace at end of life → no accumulation
⑧ Write the interval into the rules → control at the source
JJF 1001-2011 General Terms in Metrology and Their Definitions