E45-291 · Calibration · Thermocouple · ★
The cold-junction compensation was not calibrated, so at room temperature the reading is offset by a fixed 0.5mV, about 12℃
[Mechanism] The cold-junction compensation circuit itself has a zero offset and was not calibrated, so the compensation voltage is inaccurate and a fixed cold-junction error is superimposed across the whole range.
[Calculation] The cold-junction compensation zero offset is 0.5mV; for a type-K thermocouple this corresponds to about a 12℃ reading error, shifting the whole range.
[Design Omission] The cold-junction compensation was not calibrated and no ice-point comparison was performed.
① Cold-junction calibration: calibrate the cold-junction compensation zero offset → accurate reference
② Ice-point comparison: compare against a 0℃ ice point → verify the compensation
③ Temperature compensation: measure the cold-junction temperature dynamically and correct → accurate with temperature
④ Recheck: re-calibrate after a temperature change → tracking
⑤ Out-of-tolerance alarm: alarm when the error >1℃ → early warning
⑥ Periodic calibration: calibrate every quarter → prevent drift
⑦ Records: keep the compensation values on file → traceability
⑧ Write the cold-junction calibration into the procedure → control at the source
GB/T 16839.1-2018 Thermocouples - Part 1: EMF specifications and tolerances