E45-292 · Calibration · Pressure Transmitter · ★
Hysteresis was not calibrated: the up-stroke and down-stroke readings differ by 0.4%FS, leaving a large control hysteresis
[Mechanism] A sensor has hysteresis, so its up-stroke and down-stroke characteristics do not coincide; calibrating only one stroke leaves the reverse-direction measurement error uncorrected.
[Calculation] The hysteresis is 0.4%FS; after single-stroke calibration the down-stroke deviates by 0.4%FS, exceeding the 0.2% limit.
[Design Omission] No up/down-stroke hysteresis calibration and no compensation were provided.
① Hysteresis calibration: calibrate both up and down strokes → full-stroke accuracy
② Hysteresis compensation: store a hysteresis compensation term → remove the hysteresis
③ Verification: compare up and down strokes → confirm consistency
④ Out-of-tolerance alarm: alarm when hysteresis >0.2% → early warning
⑤ Periodic calibration: calibrate every quarter → prevent drift
⑥ Records: keep hysteresis records → traceability
⑦ Low-hysteresis selection: choose a low-hysteresis model → inherently better
⑧ Write the hysteresis requirement into the procedure → control at the source
GB/T 17614.1-2015 Industrial process control systems - Transmitters - Part 1: Methods of evaluating the performance