E45-296 · Calibration and Adjustment · Absolute Pressure Transmitter · ★★
A gauge-pressure standard is used to calibrate an absolute-pressure sensor; after calibration everything is off by 1atm, about 0.1MPa
[Mechanism] An absolute-pressure sensor references vacuum, but a gauge-pressure standard (referenced to atmospheric pressure) is wrongly used, so the atmospheric pressure value is not counted and the whole range shifts by one atmosphere.
[Calculation] Absolute pressure calibrated with a gauge standard differs by 101.3kPa; the whole range translates by 0.1MPa and the reading is systematically biased.
[Design Omission] Absolute and gauge pressure were not distinguished and no absolute-pressure standard was used.
① Type check: check absolute vs. gauge before calibration → correct reference
② Absolute-pressure calibration: use an absolute-pressure standard for absolute-pressure units → true reference
③ Unit check: check kPa/MPa consistency → no mixing
④ Verification: compare at the vacuum point after calibration → verify the zero
⑤ Out-of-tolerance alarm: warn when the deviation >1% → early warning
⑥ Records: keep the reference type on file → traceability
⑦ Periodic calibration: calibrate every quarter → prevent drift
⑧ Write the type-check requirement into the procedure → control at the source
GB/T 17614.1-2015 Industrial process control systems - Transmitters - Part 1: Methods of evaluating the performance