E45-330 · Environmental Protection and Temperature/Humidity · Photoelectric Sensor · ★★
In a cement plant, dust covers the lens and housing; heat dissipation is blocked, the body temperature rises above the rated value, the output drifts, and the detection distance shortens
[Mechanism] The dust layer both blocks the optical path and attenuates the signal, and wraps the housing as a thermal insulation layer that worsens heat dissipation; the body temperature rises above the rated value and the electronics drift.
[Calculation] The thermal resistance of a 1mm dust layer raises the case temperature by about 15℃; added to an ambient of 45℃ this reaches 60℃, close to the rating. Dust on the lens cuts luminous flux by 40% and shrinks the detection distance to 0.6 times.
[Design Omission] The dust duty was not assessed, and there were no dust-protection or cleaning measures.
① Protection matching: for dusty duty → choose IP65 with a smooth stainless-steel housing → reduce dust buildup
② Air-curtain purge: add a compressed-air curtain in front of the lens → continuously blow away floating dust
③ Heat-dissipation assurance: add cooling fins to the housing and clean the dust regularly → maintain heat dissipation
④ Distance margin: select the detection distance with a ×0.6 derating for dust buildup → leave headroom for attenuation
⑤ Lens protection: add a dust-proof window and wipe it regularly → keep the luminous flux
⑥ Temperature monitoring: alarm when the case temperature > rating → early warning of overheating
⑦ Cleaning interval: clean the dust on a regular (weekly) schedule and record it → prevent buildup
⑧ Selection standardization: write the dust class and cleaning method into the selection table → control at the source
GB/T 4208-2017 Degrees of protection provided by enclosures (IP code)