E45-331 · Environmental Protection and Temperature/Humidity · Temperature Sensor · ★★
An outdoor air-temperature sensor in direct sunlight reads 8℃ above the actual air temperature, with the largest deviation at noon
[Mechanism] Solar radiation heats the sensor probe housing directly, and the heat conducts to the temperature-sensing element, so the reading reflects the temperature of the sunlit probe rather than the true air temperature.
[Calculation] Strong sunlight provides about 1000W/m²; absorbed by the black probe it raises the surface temperature by 8~10℃, matching the measured 8℃ deviation.
[Design Omission] No radiation shield was fitted, leaving the probe directly exposed to sunlight.
① Radiation shield: add a louvered radiation shield → blocks sunlight while admitting air
② Forced ventilation: add a small fan inside the shield → the probe tracks the air temperature
③ Surface treatment: give the probe a white high-reflectance coating → reduce radiation absorption
④ Installation location: mount in a shaded, ventilated spot → avoid direct sunlight
⑤ Dual-probe comparison: add a shaded reference probe for comparison → identify the radiation bias
⑥ Time-of-day correction: build a sunlight-versus-deviation model for software correction → compensate the bias
⑦ Field verification: compare against a shaded reference at noon to confirm → data verification
⑧ Selection standardization: write the requirement for a radiation shield on outdoor temperature measurement into the specification → control at the source
GB/T 33693-2017 Specifications for automatic weather station observation