E45-364 · Environmental Protection and Temperature/Humidity · Temperature Sensor · ★★
A slight refrigerant leak at a chiller's temperature probe causes a localized flash-freeze down to -40℃, embrittling and cracking the probe sheath so liquid enters and it fails
[Mechanism] Leaking liquid refrigerant vaporizes rapidly and absorbs heat, dropping the local temperature sharply; an ordinary sheath embrittles at low temperature, cracks, and lets liquid in, shorting the circuit.
[Calculation] The temperature at the leak drops sharply to -40℃, below the sheath's embrittlement point of -20℃; the sheath cracks and the insulation fails.
[Design Deficiency] The sheath material was chosen for room temperature, and the flash-freeze risk from a refrigerant leak was never evaluated.
① Low-temperature sheath: choose a silicone rubber sheath rated to -60℃ → resist embrittlement cracking
② Leak protection: add a leak-proof liquid baffle at the probe → block refrigerant
③ Sealed potting: seal the joint with low-temperature potting compound → prevent liquid ingress
④ Flexible material: choose a cold-resistant flexible cable → resist freezing stiff
⑤ Leak monitoring: add a refrigerant leak alarm interlock → early detection
⑥ Location avoidance: install away from leak-prone joints → less exposure to freezing
⑦ Low-temperature verification: run a -40℃ low-temperature impact test to confirm → data confirmation
⑧ Selection standardization: write the refrigerant flash-freeze condition into the selection criteria → control at the source
GB/T 2423.1-2008 Environmental testing for electric and electronic products - Low temperature test