MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

On this page

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Common Formulas › Heat Transfer

Common Formulas · Heat Transfer (Quick-Reference Handbook)

Flat and Cylindrical Wall Conduction (Fourier's Law)

[Fourier's Law]

q = -λ·dT/dx

q — heat flux (W/m^2)

lambda — thermal conductivity (W/(m.K))

dT/dx — temperature gradient

[Single-Layer Flat Wall]

Q = λ·A·(T1-T2)/δ

q = λ·(T1-T2)/δ

delta — wall thickness (m)

A — area (m^2)

[Multi-Layer Flat Wall]

Q = (T1-Tn+1)/(Σ(δi/(λi·A)))

Total thermal resistance R = Sigma(delta_i / lambda_i)

Q = A·ΔT/R

[Cylindrical Wall Conduction]

Single layer: Q = 2pi dot lambda dot L dot (T1 - T2) / ln(r2/r1)

Multi-layer: Q = 2pi dot L dot (T1 - Tn+1) / Sigma(ln(r_i+1 / r_i) / lambda_i)

L — cylinder length

r1, r2 — inner, outer radius

[Common Material Conductivity lambda (W/(m.K))]

Silver: 429

Copper: 398

Aluminum: 237

Brass: 109

Steel (carbon): 45~55

Stainless steel: 14~16

Cast iron: 40~50

Titanium: 15

Aluminum bronze: 56

Ceramic: 1~2

Glass: 0.7~1.1

Concrete: 1.0~1.5

Rubber: 0.15

Plastic: 0.1~0.3

Insulation: <0.05

Air: 0.026

[Contact Thermal Resistance]

Solid contact surfaces have tiny gaps

Contact resistance Rc = 1 / (hc dot A)

hc — contact heat transfer coefficient (W/(m^2.K))

Rough-machined metal: hc = 2000~5000

Fine-machined metal: hc = 5000~15000

Vacuum: hc = 100~500

[Reduce Contact Resistance]

(1) Improve surface roughness

(2) Increase contact pressure

(3) Apply thermal grease

(4) Add soft-metal shim (indium / copper foil)

[Calculation Example]

Steel plate delta = 10 mm, lambda = 50, A = 1 m^2, Delta_T = 50 C

Q = 50×1×50/0.01 = 250000W = 250kW

[Applications]

Furnace wall heat transfer / pipe insulation / electronics cooling / building energy saving / cold storage design

Convective Heat Transfer (Newton's Law of Cooling)

[Newton's Law of Cooling]

Q = h·A·(Tw-Tf)

q = h·(Tw-Tf)

h — convection coefficient (W/(m^2.K))

A — heat transfer area (m^2)

Tw — wall temperature

Tf — fluid temperature

[Convection Coefficient h Reference]

Natural convection air: 5~25

Forced convection air: 25~250

Natural convection water: 100~1000

Forced convection water: 500~10000

Boiling water: 2500~50000

Condensing steam: 5000~100000

Liquid metal: 5000~25000

[Nu Correlation]

Nu = h·L/λ

Nu — Nusselt number

L — characteristic length

lambda — fluid conductivity

[Natural Convection]

Nu = C·(Gr·Pr)^n

Gr = g dot beta dot Delta_T dot L^3 / nu^2 Grashof number

Pr = nu / a Prandtl number

Vertical plate (laminar, GrPr < 10^9): C = 0.59, n = 1/4

Vertical plate (turbulent, GrPr > 10^9): C = 0.10, n = 1/3

Horizontal cylinder: C = 0.53, n = 1/4 (laminar)

[Forced Convection (internal flow)]

Laminar (Re < 2300): Nu = 3.66 (const wall T) or Nu = 4.36 (const heat flux)

Turbulent (Re > 10000, Dittus-Boelter):

Nu = 0.023·Re^0.8·Pr^n

Heating fluid: n = 0.4

Cooling fluid: n = 0.3

Re = u dot d / nu Reynolds number

Re < 2300 laminar

2300 < Re < 10000 transition

Re > 10000 turbulent

[Cross Flow (single tube)]

Nu = C·Re^n·Pr^(1/3)

Different Re ranges give different C, n

[Heat Transfer Enhancement]

(1) Increase area (finned tube)

(2) Increase coefficient (turbulence / inserts)

(3) Increase temperature difference

(4) Reduce fouling resistance (cleaning)

(5) Use high-conductivity material

[Phase-Change Heat Transfer]

Condensation: filmwise vs dropwise (dropwise h 10x higher)

Boiling: nucleate (high h) -> critical heat flux -> film (low h, dangerous)

[Applications]

Heat exchanger design, radiators, condensers, evaporators, cooling towers

Thermal Radiation (Stefan-Boltzmann Law)

[Stefan-Boltzmann Law]

Q = ε·σ·A·T⁴

epsilon — emissivity (0~1)

sigma — Stefan-Boltzmann constant = 5.67 x 10^-8 W/(m^2.K^4)

T — absolute temperature (K)

A — surface area (m^2)

[Radiation Between Two Surfaces]

Q12 = σ·A1·F12·(T1⁴-T2⁴)/(1/ε1+(1-ε2)/ε2·A1/A2)

Simplified (two infinite parallel plates, A1 = A2):

Q = σ·A·(T1⁴-T2⁴)/(1/ε1+1/ε2-1)

F12 — view factor (fraction of radiation from surface 1 to 2)

[Common Material Emissivity epsilon (room temp)]

Polished silver: 0.02

Polished aluminum: 0.04

Polished copper: 0.04

Alumina: 0.3

Polished steel: 0.07

Oxidized steel: 0.8

Cast iron (oxidized): 0.7

Black paint: 0.95

White paint: 0.90

Brick: 0.93

Wood: 0.9

Water: 0.95

Snow: 0.82

Human skin: 0.98

[View Factor Properties]

(1) Reciprocity: A1 dot F12 = A2 dot F21

(2) Completeness: Sigma Fij = 1 (enclosed space)

[Typical View Factors]

Two infinite parallel plates: F12 = 1

Small object in large enclosure: F12 = 1

Two perpendicular adjacent faces: F12 = 1/4 (equal squares)

[Radiation-Convection Combined]

Total Q = Qconv + Qrad = (hc + hr) dot A dot Delta_T

hr — radiation equivalent coefficient

hr = ε·σ·(T1+T2)·(T1²+T2²)

[Reduce Radiation Heat Loss]

(1) Low-emissivity surface (foil / polished metal)

(2) Multilayer insulation (MLI): multi-layer foil + spacers

(3) Radiation shield: high-reflectivity plate between surfaces

epsilon = 0.05 shield cuts 95% radiation

[Enhance Radiation Dissipation]

(1) High-emissivity surface (black paint / anodizing)

(2) Increase area (fins)

(3) Increase temperature difference

[Applications]

High-temp furnace radiation, solar collector, satellite thermal control, building insulation, thermocouple radiation shielding, human body dissipation

Heat Transfer Process and Heat Exchanger Calculation

[Overall Heat Transfer Coefficient K]

1/K = 1/h1 + δw/λw + 1/h2 + Rf

h1, h2 — convection coefficients on both sides

delta_w / lambda_w — wall thermal resistance

Rf — fouling resistance (m^2.K/W)

[Heat Exchanger Duty]

Q = K·A·ΔTm

Delta_Tm — mean temperature difference

[Log-Mean Temperature Difference (LMTD)]

ΔTm = (ΔT1-ΔT2)/ln(ΔT1/ΔT2)

Parallel flow: Delta_T1 = Th,in - Tc,in, Delta_T2 = Th,out - Tc,out

Counter flow: Delta_T1 = Th,in - Tc,out, Delta_T2 = Th,out - Tc,in

Cross / mixed flow: Delta_Tm = psi dot Delta_Tm_counter

psi — correction factor (0.8~1.0, from chart)

[NTU Method (epsilon-NTU)]

epsilon = 1 - exp(-NTU) (parallel, C* arbitrary)

epsilon = (1 - exp(-NTU dot (1 - C*))) / (1 - C* dot exp(-NTU dot (1 - C*))) (counter)

epsilon — effectiveness = actual / max possible duty

NTU = KA / Cmin number of transfer units

C* = Cmin / Cmax heat capacity ratio

C = m dot cp fluid heat capacity (W/K)

[Heat Exchanger Design Steps]

(1) Determine duty Q = m dot cp dot Delta_T

(2) Select type (shell-tube / plate / double-pipe / finned-tube)

(3) Compute Delta_Tm

(4) Estimate K -> compute A -> select model

(5) Check K and pressure drop

[Shell-Tube K Reference]

Water-water: 500~1500 W/(m^2.K)

Water-oil: 100~350

Steam-water: 1000~4000

Air-air: 10~40

Air-water: 20~60

[Fouling Resistance Rf Reference (m^2.K/W)]

Tap water: 0.0002

River water: 0.0006

Seawater: 0.0001

Steam: 0.0001

Compressed air: 0.0004

Lubricating oil: 0.0002

[Plate Heat Exchanger Features]

High coefficient (3000~7000 W/(m^2.K))

Compact, washable

But low pressure rating (<2.5 MPa), poor sealing

[Heat Exchanger Enhancement]

(1) Enhanced tube (internal fin / spiral / roughened)

(2) Twisted tape / vortex generator

(3) Nanofluid

(4) Electric field enhancement

(5) Surface porosity (boiling enhancement)

Other quick references in this series:Mechanics FundamentalsFluid MechanicsVibrationThermodynamicsElectrical FundamentalsQuick-Calc FormulasHydraulics / Inertia CalculationGear StrengthShaft StrengthKeyed ConnectionsSpringsBolt StrengthWeld StrengthBeam and Plate Bending

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL