Standard Equipment · Heat Exchange & Thermal (Quick Reference)
Shell-and-Tube Heat Exchanger Selection Calculation
【Area】A=Q/(K×ΔT_m)
【K Value】Water-water 800~2000, steam-water 1500~4000, water-oil 100~300, gas-water 20~60 W/m²·K
【Baffle】Segmental baffle spacing 0.2~1.0D, cut ratio 20%~25%, spacing ≥50mm and ≤D
Plate Heat Exchanger Selection
【Features】Heat transfer coefficient 3000~7000 W/m²·K, footprint is 1/3 of a shell-and-tube unit, and it can be cleaned
【Parameters】Plates 304/316L/titanium/Hastelloy, gaskets NBR/EPDM/FKM, temperature -20~200℃, pressure ≤2.5MPa
【Applications】Heating / air conditioning / chemical / food; not suitable for media containing solid particles or with high viscosity
Related quick references: Pump Selection & DesignFans & CompressorsPressure VesselsPiping & Pipe FittingsLifting & Handling