Knowledge Base › Standard Equipment Explained › Electrical Components

Standard Equipment Explained · Electrical Components (Quick Reference Manual)

Schneider Circuit Breaker Selection and Specifications

[Schneider Circuit Breaker Series]

1. iC60 (miniature, 1-pole~4-pole)

Current: 1~63A

Breaking capacity: 6~10kA

Residential / small equipment

2. iDPN (1-pole + N)

Current: 1~32A

Compact

3. Acti9 (high-performance miniature)

Current: 1~63A

Breaking capacity: 10~36kA

4. NSX (molded case, most common)

Current: 16~160A

Breaking capacity: 36~100kA

5. NS (molded case, legacy series)

Current: 16~630A

6. Compact NSX

Current: 100~630A

7. Masterpact (frame type)

Current: 630~6300A

High current

[NSX Specifications (molded case)]

Model | Current (A) | Breaking capacity (kA) | Poles | Size

NSX100 | 16~100 | 36/50/70/100 | 3/4 | Standard

NSX160 | 25~160 | 36/50/70/100 | 3/4 | Standard

NSX250 | 40~250 | 36/50/70/100 | 3/4 | Standard

NSX400 | 160~400 | 36/50 | 3/4 | Large

NSX630 | 250~630 | 36/50 | 3/4 | Large

[Trip Unit Types]

1. TM-D (thermal-magnetic)

Thermal overload (adjustable) + magnetic short-circuit (adjustable)

Simple, economical

Suitable for: cable / motor protection

2. Micrologic (electronic)

Long delay + short delay + instantaneous + ground fault

Accurate, full-featured

Suitable for: critical equipment

[Motor Protection Circuit Breaker]

GV2/GV3 series

Current: 0.16~32A

Setting: 0.63~1× In

Magnetic protection: 13× In, fixed

Functions:

- Thermal overload (adjustable)

- Short-circuit (fixed)

- Phase-loss protection

- Optional auxiliary contacts

[Selection Principles]

1. Rated current

In ≥ I_load

Leave 10~20% margin

2. Breaking capacity

Icu ≥ system short-circuit current

Common: 6/10/15/25/36/50kA

3. Number of poles

1P: single-phase

1P+N: single-phase with N

3P: three-phase

4P: three-phase + N (when required)

4. Trip unit

- Thermal-magnetic (simple)

- Electronic (accurate)

5. Application

- Distribution protection

- Motor protection (dedicated type)

- Lighting protection

[Calculation Example]

Motor: 7.5kW, 4-pole, 380V, 15A

1. Select the motor protection circuit breaker

In ≥ 1.25×15 = 18.75A

Select GV2ME22 (18~25A, adjustable)

Setting: 18A

2. Short-circuit protection

The breaking capacity must exceed the short-circuit current

6~10kA is sufficient for general applications

3. Coordinate with a contactor + a thermal overload relay

GV2+LC1D18+LRD18

Or use a GV2 (thermal protection already included)

Schneider Contactor and Thermal Overload Relay Selection

[Schneider Contactor Series]

TeSys D series (most common):

LC1D09~LC1D150

Model code: LC1D18P7

LC1 — contactor

D — series (D series)

18 — current rating (18A)

P — voltage (AC220V)

7 — Auxiliary contacts (1NO+1NC)

[LC1D Specifications]

Model | AC-3 current (A) | Control power (kW, 400V) | Coil voltage

LC1D09 | 9 | 4 | 24/48/110/220V

LC1D12 | 12 | 5.5 | Same as above

LC1D18 | 18 | 7.5 | Same as above

LC1D25 | 25 | 11 | Same as above

LC1D32 | 32 | 15 | Same as above

LC1D38 | 38 | 18.5 | Same as above

LC1D40 | 40 | 18.5 | Same as above

LC1D50 | 50 | 22 | Same as above

LC1D65 | 65 | 30 | Same as above

LC1D80 | 80 | 37 | Same as above

LC1D95 | 95 | 45 | Same as above

LC1D115 | 115 | 55 | Same as above

LC1D150 | 150 | 75 | Same as above

LC1D170 | 170 | 90 | Same as above

LC1D205 | 205 | 110 | Same as above

LC1D245 | 245 | 132 | Same as above

LC1D300 | 300 | 160 | Same as above

LC1D410 | 410 | 220 | Same as above

LC1D475 | 475 | 250 | Same as above

LC1D620 | 620 | 330 | Same as above

LC1D780 | 780 | 400 | Same as above

[Utilization Categories]

AC-1: Non-inductive loads (heaters)

AC-2: Starting/stopping of slip-ring motors

AC-3: Starting/stopping of squirrel-cage motors (most common)

AC-4: Frequent starting/plugging of squirrel-cage motors

AC-15: Control circuits (low current)

AC-3 current < AC-1 current

[Thermal Overload Relay LRD Series]

Model | Current range (A) | Matching contactor

LRD07 | 1.6~2.5 | LC1D09

LRD08 | 2.5~4 | LC1D09

LRD10 | 4~6 | LC1D09

LRD12 | 5.5~8 | LC1D09

LRD14 | 7~10 | LC1D09

LRD16 | 9~13 | LC1D12

LRD21 | 12~18 | LC1D18

LRD22 | 13~17 | LC1D18

LRD32 | 23~32 | LC1D32

LRD3353 | 30~40 | LC1D40

LRD3357 | 37~50 | LC1D50

LRD3363 | 48~65 | LC1D65

LRD3365 | 55~70 | LC1D80

[Thermal Overload Relay Functions]

1. Overload protection (I²t)

2. Phase-loss protection

3. Manual/automatic reset

4. Trip class: 10A/10/20/30

Class 10: trips within 4~10 s at 7.2In

Class 20: 6~20 s at 7.2In (heavy-duty starting)

Class 30: 9~30 s at 7.2In (high inertia)

[Selection Coordination]

Motor power → current → contactor + thermal relay + circuit breaker

7.5 kW motor (15A):

Circuit breaker: GV2ME22 (18~25A)

Contactor: LC1D18 (18A)

Thermal relay: LRD21 (12~18A), set to 15A

15 kW motor (29A):

Circuit breaker: GV2ME32 (24~32A)

Contactor: LC1D32 (32A)

Thermal relay: LRD32 (23~32A), set to 29A

[Mounting Forms]

1. Standalone mounting

2. Mounted directly below the contactor

(The LRD series mounts directly onto the LC1D)

3. DIN-rail mounting

[Accessories]

1. Auxiliary contacts

LA1DN20(2NO)

LA1DN02(2NC)

LA1DN11(1NO+1NC)

2. Mechanical interlocking

LA9D5098 (interlocks 2 contactors)

Essential for forward/reverse

3. Surge suppression

LA4DA1U (varistor)

Coil protection

[Selection Steps]

1. Determine motor power/current

2. Select the contactor (AC-3 current ≥ 1.2 I_motor)

3. Select the thermal relay (current range must include I_motor)

4. Select the circuit breaker (motor-protection type)

5. Select the coil voltage (matched to the control supply)

6. Add auxiliary contacts (as control requires)

7. Mechanical interlock (forward/reverse)

8. Surge suppression (AC coil)

Switching Power Supply and Voltage Regulator Selection

[MEAN WELL Switching Power Supply Series]

1. LRS (economy)

LRS-35: 35W

LRS-50: 50W

LRS-75: 75W

LRS-100: 100W

LRS-150: 150W

LRS-200: 200W

LRS-350: 350W

LRS-450: 450W

LRS-600: 600W

LRS-1000: 1000W

LRS-1500: 1500W

LRS-2000: 2000W

LRS-3000: 3000W

2. MDR (DIN-rail)

MDR-20/40/60/120/240

DIN-rail mounting

3. NDR (high-performance DIN-rail)

NDR-120/240/480

4. UHP (ultra-slim)

UHP-200A/500A/1000A

Compact

[Specifications (220V input, 24V output)]

Model | Power (W) | Output current (A) | Dimensions (W×H×D mm) | Efficiency

LRS-50 | 50 | 2.2 | 100×125×32 | 89%

LRS-100 | 100 | 4.5 | 100×125×32 | 89%

LRS-150 | 150 | 7 | 159×97×30 | 89%

LRS-200 | 200 | 8.8 | 199×98×32 | 90%

LRS-350 | 350 | 15 | 215×115×30 | 90%

LRS-450 | 450 | 20 | 238×115×30 | 91%

LRS-600 | 600 | 27 | 238×115×30 | 93%

LRS-1000 | 1000 | 44 | 283×128×40 | 94%

LRS-1500 | 1500 | 67.5 | 325×128×82 | 94%

LRS-2000 | 2000 | 89 | 326×128×82 | 94%

LRS-3000 | 3000 | 135 | 360×218×88 | 95%

[Input Voltage]

AC 85~132V / 170~264V (auto switching)

DC 120~370V

Frequency: 47~63Hz

[Output Voltage]

DC 5V, 12V, 15V, 24V, 48V

Adjustable range: ±10%

[Protection Functions]

1. Overvoltage protection (OVP)

110~135% of rated

Shutdown

2. Overcurrent protection (OCP)

105~135% of rated

Hiccup mode

3. Overtemperature protection (OTP)

>85~115℃ (internal)

Shutdown

4. Short-circuit protection

Hiccup / constant current

[Characteristics]

1. High efficiency (89~95%)

2. Wide input range

3. Built-in EMC filtering

4. Forced-air cooling (high power)

5. Operating temperature -25~+70℃ (with derating)

6. Safety certifications: UL/CB/CE/CCC

7. Service life >50,000 hours

8. Parallel operation (for high-power selection)

[Selection Steps]

1. Calculate the total load current

I_total = ΣIi × K_utilization

K = 0.7~0.8 (simultaneity factor)

2. Leave a 20~30% margin

P_supply ≥ 1.2~1.3 × P_load

3. Select voltage

24V (most common)

12V/5V (electronics)

4. Choose the mounting method

- DIN rail

- Screw fixing

- Base plate mounting

5. Choose the protection rating

- IP20 (inside the cabinet)

- IP65 (on-site)

6. Redundant design (important)

Parallel connection + diode module

[Calculation Example]

Loads: PLC (2A) + touch panel (1A) + sensors (1A) + solenoid valves (5A)

Total current: 2+1+1+5 = 9A

Simultaneity factor 0.8: 9×0.8 = 7.2A

Margin 1.3: 7.2×1.3 = 9.36A

Select LRS-350 (15A, 350W)

Adequate margin

[Installation Notes]

1. Ventilation and heat dissipation (50 mm clearance above and below)

2. Reliable grounding

3. Add a circuit breaker on the input side

4. Add a fuse on the output side

5. Add an EMC filter for high power

6. Use thicker wire for long runs

7. Watch current sharing when paralleling

8. Temperature monitoring (derating at high temperature)

Servo Drive Commissioning and Optimization

[Servo Drive Functions]

1. Position control

Pulse + direction

Electronic gear ratio

2. Speed control

Analog ±10V

Internal speed

3. Torque control

Analog ±10V

Speed limit

[Electronic Gear Ratio]

Motor encoder resolution: N_encoder (pulses/rev)

Command pulses: N_command

Electronic gear ratio = N_encoder/(N_command×i)

i — reduction ratio

Example: 17-bit encoder = 131072, command 10000 pulses/rev

Gear ratio = 131072/10000 = 13.1072

[Gain Tuning]

1. Position-loop gain Kp

Response speed

Too high causes oscillation

2. Speed-loop gain Kv

Speed response

Too high causes oscillation

3. Speed-loop integral Ti

Eliminates steady-state error

Too large causes overshoot

4. Feedforward compensation

Reduces following error

Speed feedforward + acceleration feedforward

[Filters]

1. Low-pass filter

Filters high-frequency noise

2. Notch filter

Suppress resonance at a specific frequency

Automatically detect the resonance frequency

3. Vibration suppression control

Multi-degree-of-freedom vibration suppression

[Auto-Tuning Procedure]

1. Measure inertia

2. Calculate gains

3. Test the response

4. Fine-tune and optimize

5. Save parameters

[Commissioning Tools]

Yaskawa: SigmaWin+

Panasonic: PANATERM

Mitsubishi: MR Configurator2

Siemens: Starter/TIA

Huichuan: Inovance

[Common Issues]

1. Oscillation

- Lower gain

- Add notch

- Check mechanics

2. Overshoot

- Lower gain

- Increase the integral time

- Add feedforward

3. Large following error

- Increase gain

- Add feedforward

- Check load

4. Noise

- Filter

- Check grounding

- Shielded cable

Intermediate Relay and Time Relay Selection

[Intermediate Relays]

Function: signal amplification, logic isolation, extra contacts

Model (Schneider):

RXM2LB2BD

RXM — series

2 — contact count (2 changeover)

LB — socket

2BD — 2 changeover contacts + diode

Coil: DC24V

Contact configuration:

2C/O (2 normally open)

2C/O + 2NC (mixed)

4C/O (4 normally open)

Coil voltage: DC12/24V, AC24/110/220V

Contact rating:

Resistive: 5A 250VAC

Inductive: 2A 250VAC

Mechanical life: >10⁷ operations

Electrical life: >10⁶ operations (at rated load)

[Time Relays]

Function: delayed switching

Types:

1. ON delay

T1: after energization, the contacts operate after a delay of T1

2. OFF delay

The contacts operate after a delay following de-energization

3. ON/OFF delay

4. Star-delta delay

Star-delta motor starting

Model (Schneider RE17):

RE17R1MW

R1 — single function (ON delay)

MW — multi-range

Time range:

0.1~3s

0.3~10s

1~100s

10s~10min

Accuracy: ±1~5%

[Selection]

1. Number of contacts

2. Coil voltage

3. Delay type

4. Delay range

5. Mounting (DIN rail)

6. Restart function

[Applications]

1. Star-delta motor starting

Switchover after a 30 s ON delay

2. Sequential starting

Start multiple devices in sequence

3. Fault-alarm delay

Avoid transient interference

4. Automatic cycling

Cycle control

Surge Protective Devices and EMC Filtering

[Surge Protective Device (SPD)]

Function: protect equipment from damage by lightning and switching overvoltages

Classification:

1. Type 1 (T1)

Lightning current discharge

10/350μs waveform

Installed at main incoming line

2. Type 2 (T2)

Switching overvoltage

8/20μs waveform

Installed at distribution board

3. Type 3 (T3)

Fine protection at terminal

Before equipment

[Selection]

1. In (nominal discharge current)

T1: 15kA

T2: 20~40kA

T3: 5kA

2. Up (voltage protection level)

< device withstand voltage

3. Number of poles

1P/2P/3P/4P

[EMC Filters]

Function: suppress electromagnetic interference (EMI)

Types:

1. Input filter

VFD input line

Suppresses conducted interference

2. Output filter

VFD output line

For long cable runs

3. DC filter

DC bus

[VFD EMC]

1. Incoming-line EMC filter

Suppress interference to the grid

2. Output dU/dt filter

Protects motor insulation

3. Sine-wave filter

Output close to sinusoidal

Long cable

4. Shielded cable

Shield grounding for signal lines

Power cable shield

5. Grounding

Reliable PE

Equipotential

[Installation]

1. Keep the SPD close to the incoming line

2. Keep the filter close to the VFD

3. Ground the shield 360°

4. Route input and output cables separately

5. Use twisted shielded signal cables

Other quick references in this series:Servo MotorGearboxVariable Frequency DriveCylinderPneumatic ComponentsHydraulic ComponentsSensorPLCTouchscreenCouplingBearingValveMotor