1. iC60 (miniature, 1-pole~4-pole)
Current: 1~63A
Breaking capacity: 6~10kA
Residential / small equipment
2. iDPN (1-pole + N)
Current: 1~32A
Compact
3. Acti9 (high-performance miniature)
Current: 1~63A
Breaking capacity: 10~36kA
4. NSX (molded case, most common)
Current: 16~160A
Breaking capacity: 36~100kA
5. NS (molded case, legacy series)
Current: 16~630A
6. Compact NSX
Current: 100~630A
7. Masterpact (frame type)
Current: 630~6300A
High current
Model | Current (A) | Breaking capacity (kA) | Poles | Size
NSX100 | 16~100 | 36/50/70/100 | 3/4 | Standard
NSX160 | 25~160 | 36/50/70/100 | 3/4 | Standard
NSX250 | 40~250 | 36/50/70/100 | 3/4 | Standard
NSX400 | 160~400 | 36/50 | 3/4 | Large
NSX630 | 250~630 | 36/50 | 3/4 | Large
1. TM-D (thermal-magnetic)
Thermal overload (adjustable) + magnetic short-circuit (adjustable)
Simple, economical
Suitable for: cable / motor protection
2. Micrologic (electronic)
Long delay + short delay + instantaneous + ground fault
Accurate, full-featured
Suitable for: critical equipment
GV2/GV3 series
Current: 0.16~32A
Setting: 0.63~1× In
Magnetic protection: 13× In, fixed
Functions:
- Thermal overload (adjustable)
- Short-circuit (fixed)
- Phase-loss protection
- Optional auxiliary contacts
1. Rated current
In ≥ I_load
Leave 10~20% margin
2. Breaking capacity
Icu ≥ system short-circuit current
Common: 6/10/15/25/36/50kA
3. Number of poles
1P: single-phase
1P+N: single-phase with N
3P: three-phase
4P: three-phase + N (when required)
4. Trip unit
- Thermal-magnetic (simple)
- Electronic (accurate)
5. Application
- Distribution protection
- Motor protection (dedicated type)
- Lighting protection
Motor: 7.5kW, 4-pole, 380V, 15A
1. Select the motor protection circuit breaker
In ≥ 1.25×15 = 18.75A
Select GV2ME22 (18~25A, adjustable)
Setting: 18A
2. Short-circuit protection
The breaking capacity must exceed the short-circuit current
6~10kA is sufficient for general applications
3. Coordinate with a contactor + a thermal overload relay
GV2+LC1D18+LRD18
Or use a GV2 (thermal protection already included)
TeSys D series (most common):
LC1D09~LC1D150
Model code: LC1D18P7
LC1 — contactor
D — series (D series)
18 — current rating (18A)
P — voltage (AC220V)
7 — Auxiliary contacts (1NO+1NC)
Model | AC-3 current (A) | Control power (kW, 400V) | Coil voltage
LC1D09 | 9 | 4 | 24/48/110/220V
LC1D12 | 12 | 5.5 | Same as above
LC1D18 | 18 | 7.5 | Same as above
LC1D25 | 25 | 11 | Same as above
LC1D32 | 32 | 15 | Same as above
LC1D38 | 38 | 18.5 | Same as above
LC1D40 | 40 | 18.5 | Same as above
LC1D50 | 50 | 22 | Same as above
LC1D65 | 65 | 30 | Same as above
LC1D80 | 80 | 37 | Same as above
LC1D95 | 95 | 45 | Same as above
LC1D115 | 115 | 55 | Same as above
LC1D150 | 150 | 75 | Same as above
LC1D170 | 170 | 90 | Same as above
LC1D205 | 205 | 110 | Same as above
LC1D245 | 245 | 132 | Same as above
LC1D300 | 300 | 160 | Same as above
LC1D410 | 410 | 220 | Same as above
LC1D475 | 475 | 250 | Same as above
LC1D620 | 620 | 330 | Same as above
LC1D780 | 780 | 400 | Same as above
AC-1: Non-inductive loads (heaters)
AC-2: Starting/stopping of slip-ring motors
AC-3: Starting/stopping of squirrel-cage motors (most common)
AC-4: Frequent starting/plugging of squirrel-cage motors
AC-15: Control circuits (low current)
AC-3 current < AC-1 current
Model | Current range (A) | Matching contactor
LRD07 | 1.6~2.5 | LC1D09
LRD08 | 2.5~4 | LC1D09
LRD10 | 4~6 | LC1D09
LRD12 | 5.5~8 | LC1D09
LRD14 | 7~10 | LC1D09
LRD16 | 9~13 | LC1D12
LRD21 | 12~18 | LC1D18
LRD22 | 13~17 | LC1D18
LRD32 | 23~32 | LC1D32
LRD3353 | 30~40 | LC1D40
LRD3357 | 37~50 | LC1D50
LRD3363 | 48~65 | LC1D65
LRD3365 | 55~70 | LC1D80
1. Overload protection (I²t)
2. Phase-loss protection
3. Manual/automatic reset
4. Trip class: 10A/10/20/30
Class 10: trips within 4~10 s at 7.2In
Class 20: 6~20 s at 7.2In (heavy-duty starting)
Class 30: 9~30 s at 7.2In (high inertia)
Motor power → current → contactor + thermal relay + circuit breaker
7.5 kW motor (15A):
Circuit breaker: GV2ME22 (18~25A)
Contactor: LC1D18 (18A)
Thermal relay: LRD21 (12~18A), set to 15A
15 kW motor (29A):
Circuit breaker: GV2ME32 (24~32A)
Contactor: LC1D32 (32A)
Thermal relay: LRD32 (23~32A), set to 29A
1. Standalone mounting
2. Mounted directly below the contactor
(The LRD series mounts directly onto the LC1D)
3. DIN-rail mounting
1. Auxiliary contacts
LA1DN20(2NO)
LA1DN02(2NC)
LA1DN11(1NO+1NC)
2. Mechanical interlocking
LA9D5098 (interlocks 2 contactors)
Essential for forward/reverse
3. Surge suppression
LA4DA1U (varistor)
Coil protection
1. Determine motor power/current
2. Select the contactor (AC-3 current ≥ 1.2 I_motor)
3. Select the thermal relay (current range must include I_motor)
4. Select the circuit breaker (motor-protection type)
5. Select the coil voltage (matched to the control supply)
6. Add auxiliary contacts (as control requires)
7. Mechanical interlock (forward/reverse)
8. Surge suppression (AC coil)
1. LRS (economy)
LRS-35: 35W
LRS-50: 50W
LRS-75: 75W
LRS-100: 100W
LRS-150: 150W
LRS-200: 200W
LRS-350: 350W
LRS-450: 450W
LRS-600: 600W
LRS-1000: 1000W
LRS-1500: 1500W
LRS-2000: 2000W
LRS-3000: 3000W
2. MDR (DIN-rail)
MDR-20/40/60/120/240
DIN-rail mounting
3. NDR (high-performance DIN-rail)
NDR-120/240/480
4. UHP (ultra-slim)
UHP-200A/500A/1000A
Compact
Model | Power (W) | Output current (A) | Dimensions (W×H×D mm) | Efficiency
LRS-50 | 50 | 2.2 | 100×125×32 | 89%
LRS-100 | 100 | 4.5 | 100×125×32 | 89%
LRS-150 | 150 | 7 | 159×97×30 | 89%
LRS-200 | 200 | 8.8 | 199×98×32 | 90%
LRS-350 | 350 | 15 | 215×115×30 | 90%
LRS-450 | 450 | 20 | 238×115×30 | 91%
LRS-600 | 600 | 27 | 238×115×30 | 93%
LRS-1000 | 1000 | 44 | 283×128×40 | 94%
LRS-1500 | 1500 | 67.5 | 325×128×82 | 94%
LRS-2000 | 2000 | 89 | 326×128×82 | 94%
LRS-3000 | 3000 | 135 | 360×218×88 | 95%
AC 85~132V / 170~264V (auto switching)
DC 120~370V
Frequency: 47~63Hz
DC 5V, 12V, 15V, 24V, 48V
Adjustable range: ±10%
1. Overvoltage protection (OVP)
110~135% of rated
Shutdown
2. Overcurrent protection (OCP)
105~135% of rated
Hiccup mode
3. Overtemperature protection (OTP)
>85~115℃ (internal)
Shutdown
4. Short-circuit protection
Hiccup / constant current
1. High efficiency (89~95%)
2. Wide input range
3. Built-in EMC filtering
4. Forced-air cooling (high power)
5. Operating temperature -25~+70℃ (with derating)
6. Safety certifications: UL/CB/CE/CCC
7. Service life >50,000 hours
8. Parallel operation (for high-power selection)
1. Calculate the total load current
I_total = ΣIi × K_utilization
K = 0.7~0.8 (simultaneity factor)
2. Leave a 20~30% margin
P_supply ≥ 1.2~1.3 × P_load
3. Select voltage
24V (most common)
12V/5V (electronics)
4. Choose the mounting method
- DIN rail
- Screw fixing
- Base plate mounting
5. Choose the protection rating
- IP20 (inside the cabinet)
- IP65 (on-site)
6. Redundant design (important)
Parallel connection + diode module
Loads: PLC (2A) + touch panel (1A) + sensors (1A) + solenoid valves (5A)
Total current: 2+1+1+5 = 9A
Simultaneity factor 0.8: 9×0.8 = 7.2A
Margin 1.3: 7.2×1.3 = 9.36A
Select LRS-350 (15A, 350W)
Adequate margin
1. Ventilation and heat dissipation (50 mm clearance above and below)
2. Reliable grounding
3. Add a circuit breaker on the input side
4. Add a fuse on the output side
5. Add an EMC filter for high power
6. Use thicker wire for long runs
7. Watch current sharing when paralleling
8. Temperature monitoring (derating at high temperature)
1. Position control
Pulse + direction
Electronic gear ratio
2. Speed control
Analog ±10V
Internal speed
3. Torque control
Analog ±10V
Speed limit
Motor encoder resolution: N_encoder (pulses/rev)
Command pulses: N_command
Electronic gear ratio = N_encoder/(N_command×i)
i — reduction ratio
Example: 17-bit encoder = 131072, command 10000 pulses/rev
Gear ratio = 131072/10000 = 13.1072
1. Position-loop gain Kp
Response speed
Too high causes oscillation
2. Speed-loop gain Kv
Speed response
Too high causes oscillation
3. Speed-loop integral Ti
Eliminates steady-state error
Too large causes overshoot
4. Feedforward compensation
Reduces following error
Speed feedforward + acceleration feedforward
1. Low-pass filter
Filters high-frequency noise
2. Notch filter
Suppress resonance at a specific frequency
Automatically detect the resonance frequency
3. Vibration suppression control
Multi-degree-of-freedom vibration suppression
1. Measure inertia
2. Calculate gains
3. Test the response
4. Fine-tune and optimize
5. Save parameters
Yaskawa: SigmaWin+
Panasonic: PANATERM
Mitsubishi: MR Configurator2
Siemens: Starter/TIA
Huichuan: Inovance
1. Oscillation
- Lower gain
- Add notch
- Check mechanics
2. Overshoot
- Lower gain
- Increase the integral time
- Add feedforward
3. Large following error
- Increase gain
- Add feedforward
- Check load
4. Noise
- Filter
- Check grounding
- Shielded cable
Function: signal amplification, logic isolation, extra contacts
Model (Schneider):
RXM2LB2BD
RXM — series
2 — contact count (2 changeover)
LB — socket
2BD — 2 changeover contacts + diode
Coil: DC24V
Contact configuration:
2C/O (2 normally open)
2C/O + 2NC (mixed)
4C/O (4 normally open)
Coil voltage: DC12/24V, AC24/110/220V
Contact rating:
Resistive: 5A 250VAC
Inductive: 2A 250VAC
Mechanical life: >10⁷ operations
Electrical life: >10⁶ operations (at rated load)
Function: delayed switching
Types:
1. ON delay
T1: after energization, the contacts operate after a delay of T1
2. OFF delay
The contacts operate after a delay following de-energization
3. ON/OFF delay
4. Star-delta delay
Star-delta motor starting
Model (Schneider RE17):
RE17R1MW
R1 — single function (ON delay)
MW — multi-range
Time range:
0.1~3s
0.3~10s
1~100s
10s~10min
Accuracy: ±1~5%
1. Number of contacts
2. Coil voltage
3. Delay type
4. Delay range
5. Mounting (DIN rail)
6. Restart function
1. Star-delta motor starting
Switchover after a 30 s ON delay
2. Sequential starting
Start multiple devices in sequence
3. Fault-alarm delay
Avoid transient interference
4. Automatic cycling
Cycle control
Function: protect equipment from damage by lightning and switching overvoltages
Classification:
1. Type 1 (T1)
Lightning current discharge
10/350μs waveform
Installed at main incoming line
2. Type 2 (T2)
Switching overvoltage
8/20μs waveform
Installed at distribution board
3. Type 3 (T3)
Fine protection at terminal
Before equipment
1. In (nominal discharge current)
T1: 15kA
T2: 20~40kA
T3: 5kA
2. Up (voltage protection level)
< device withstand voltage
3. Number of poles
1P/2P/3P/4P
Function: suppress electromagnetic interference (EMI)
Types:
1. Input filter
VFD input line
Suppresses conducted interference
2. Output filter
VFD output line
For long cable runs
3. DC filter
DC bus
1. Incoming-line EMC filter
Suppress interference to the grid
2. Output dU/dt filter
Protects motor insulation
3. Sine-wave filter
Output close to sinusoidal
Long cable
4. Shielded cable
Shield grounding for signal lines
Power cable shield
5. Grounding
Reliable PE
Equipotential
1. Keep the SPD close to the incoming line
2. Keep the filter close to the VFD
3. Ground the shield 360°
4. Route input and output cables separately
5. Use twisted shielded signal cables
Other quick references in this series:Servo MotorGearboxVariable Frequency DriveCylinderPneumatic ComponentsHydraulic ComponentsSensorPLCTouchscreenCouplingBearingValveMotor