Knowledge Base › Design Pitfalls › Electrical Design

Design Pitfalls · Electrical Design (Quick-Reference Handbook)

Sensor Cables Sharing a Conduit with Power Cables

Pitfall: sensor signal cables run in the same wire duct as the motor / VFD power lines

Consequence: electromagnetic interference → false signals / loss of control

Correct practice: route signal cables and power lines separately (spacing ≥200mm)

PLC Output Driving a Heavy Load Without an Interposing Relay

Pitfall: the PLC output directly drives a contactor / solenoid valve (>2A)

Consequence: the PLC contacts burn out

Correct practice: the PLC output drives an interposing relay (24V coil) → the relay contacts drive the heavy load

Wrong E-Stop Button Selection

Pitfall: an ordinary latching pushbutton (non-safety type) is used as the E-stop button

Consequence: it cannot be reliably opened after actuation → the safety circuit fails

Correct practice: the E-stop button must be a mushroom-head / red / twist-to-reset type (ISO 13850)

Motor Direct-Started at Excessive Power

Pitfall: a high-power motor (>15kW) is started direct-on-line at full voltage

Consequence: the starting current is 6~8× the rated current → voltage dip → affects other equipment

Correct practice: star-delta / soft start / VFD starting

No Signal Isolator Between the PLC and the VFD

A signal isolator (4~20mA) should be added on the PLC analog output to the VFD / without it → interference → VFD malfunctions

Signal Attenuation on an Over-Long Analog Signal Cable

When a 4~20mA signal cable is >200m, the signal attenuates / add an isolator / switch to RS485 communication / shorten the cable

Improper Shared Ground for the VFD and Servo Drive

The VFD / servo drive ground conductor should be independent / a shared ground → interference → motor jitter / ground conductor ≥4mm² / ground resistance ≤10Ω

No E-Stop Logic in the PLC Program

In addition to the hardware E-stop circuit / the PLC program should implement E-stop logic (all outputs reset on E-stop) / skipping it → the hardware cuts power but the program keeps the outputs on

PLC Input Filter Time Too Long

The PLC input filter time defaults to 10ms / fast signals (<5ms) → not detected / reduce the filter setting (1~5ms)

Ordinary Relay Used in the Safety Circuit

The safety circuit must use a safety relay (redundant + self-checking) / an ordinary relay → contact welding → the safety function fails

Stepper Motor Driver Current Mismatch

Stepper driver current set too high → the motor overheats / too low → insufficient torque / set it to the motor rated current (peak / RMS)

Bearing Electrical Erosion in VFD-Driven Motors

[Shaft Current Not Considered When a Motor Runs on a VFD] High-power VFD-driven motors (>30kW) should use insulated bearings / ignoring it → shaft current → bearing electrical erosion → abnormal noise and failure

Equipment Not Grounded

[Equipment Not Grounded → Leakage Current Injures People] The metal enclosure of equipment must be reliably grounded (ground resistance ≤4Ω) / no grounding → leakage → electric shock and fatalities

No Fuse on the PLC Output

PLC digital outputs should be fitted with fuses (0.5~1A) / no fuse → a load short circuit → the PLC module burns out → production stops

PLC Output Module Carrying Different Types of Loads

DC24V and AC220V loads must not be mixed on one PLC output module → different voltages → risk of short circuit → isolate with relays

No Wire Duct in the Electrical Control Cabinet

Cables inside the electrical control cabinet should be routed in wire ducts and fixed with cable ties / no ducts → messy → difficult maintenance

No Grounding Busbar in the Electrical Control Cabinet

The electrical control cabinet should have a grounding busbar (for centralized PE conductors) / none → poor grounding → safety risk

VFD and Controller Placed Too Close Inside the Cabinet

Keep the VFD and PLC at least 200mm apart / too close → electromagnetic interference → PLC malfunctions

Other quick references in this series:Welding PitfallsCasting PitfallsShaft System PitfallsSheet Metal PitfallsAssembly PitfallsHydraulic PitfallsPneumatic PitfallsShaft System DesignHousing DesignWelded StructuresSheet Metal StructuresSpring DesignBolted JointsBearing Arrangement

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »