Pitfall: high-current contactor (>10A) without an arc chute / RC snubber
Consequence: arcing at the contacts → burning and welding
Correct practice: add an arc chute / RC snubber circuit / varistor
Pitfall: no fuse or electronic protection on the PLC output
Consequence: a short circuit on the output → the PLC output module burns out
Correct practice: add a 0.5~1A fuse or electronic protection to each output
Pitfall: DC24V signal cable and AC220V power cable in the same duct
Consequence: electromagnetic interference → false signal operation
Correct practice: route power and signal wiring separately (spacing ≥200mm)
Pitfall: normally-open contact in the E-stop circuit (it must be energized to stop)
Consequence: the E-stop fails when power is lost
Correct practice: use a normally-closed (NC) contact with a forced-opening mechanism for the E-stop
Pitfall: protecting the motor with a fuse only
Consequence: when one phase fuses, the motor runs on single phase → burnout
Correct practice: fuse + thermal relay (phase-loss protection type)
Design pitfall: the equipment E-stop button is not located per safety standards → it cannot be found in an emergency → safety hazard / it must be prominent and easy to reach / red mushroom head