PLC output directly drives a heavy load (contactor >2A) without an interposing relay → burnt PLC contacts / use an interposing relay
The E-stop button must use a normally-closed (NC) contact with forced opening / a normally-open contact → the E-stop fails when power is lost → safety hazard
AC220V power cable and DC24V signal cable in the same duct → electromagnetic interference → false operation / separate them by ≥200mm / if crossing is unavoidable, cross at right angles
Motors >7.5kW started direct-on-line at full voltage → starting current 6~8 times rated → sharp supply voltage dip / use star-delta, soft start, or a VFD
VFD-to-motor cable >100m without an output reactor → reflected voltage waves → motor insulation damage / add a reactor or filter
A frequently started/stopped servo motor (>5 times/min) must have an external braking resistor / without it → DC bus overvoltage → drive fault
Switching power supply rating ≤ total load current → supply overload → voltage drop → equipment malfunction / rating = total load × 1.3
Analog sensor (4~20mA) cables must be shielded with the shield grounded at one end / without it → interference → signal fluctuation
VFDs and servo drives in the cabinet generate much heat / no ventilation or fan → excessive temperature → frequent equipment faults / add axial fans
A safety door should have a safety door lock (magnetic/mechanical) plus a safety relay / an ordinary limit switch instead → it can be bypassed → safety hazard