Knowledge Base › Design Pitfalls › Electrical/Control Design

Design Pitfalls · Electrical/Control Design (Quick-Reference Handbook)

No Isolation on PLC Outputs

PLC output directly drives a heavy load (contactor >2A) without an interposing relay → burnt PLC contacts / use an interposing relay

Normally-Open Contacts in the E-stop Circuit

The E-stop button must use a normally-closed (NC) contact with forced opening / a normally-open contact → the E-stop fails when power is lost → safety hazard

Power and Signal Wiring Not Separated

AC220V power cable and DC24V signal cable in the same duct → electromagnetic interference → false operation / separate them by ≥200mm / if crossing is unavoidable, cross at right angles

Direct-on-Line Motor Start at Excessive Power

Motors >7.5kW started direct-on-line at full voltage → starting current 6~8 times rated → sharp supply voltage dip / use star-delta, soft start, or a VFD

VFD Too Far From the Motor

VFD-to-motor cable >100m without an output reactor → reflected voltage waves → motor insulation damage / add a reactor or filter

Servo Motor Without a Braking Resistor

A frequently started/stopped servo motor (>5 times/min) must have an external braking resistor / without it → DC bus overvoltage → drive fault

Undersized Switching Power Supply

Switching power supply rating ≤ total load current → supply overload → voltage drop → equipment malfunction / rating = total load × 1.3

Sensor Cables Without Shielding

Analog sensor (4~20mA) cables must be shielded with the shield grounded at one end / without it → interference → signal fluctuation

Poor Heat Dissipation in the Cabinet

VFDs and servo drives in the cabinet generate much heat / no ventilation or fan → excessive temperature → frequent equipment faults / add axial fans

Safety Door Interlock Without a Safety Switch

A safety door should have a safety door lock (magnetic/mechanical) plus a safety relay / an ordinary limit switch instead → it can be bypassed → safety hazard

Other quick references in this series:Welding PitfallsCasting PitfallsShaft System PitfallsSheet Metal PitfallsAssembly PitfallsHydraulic PitfallsPneumatic PitfallsShaft System DesignHousing DesignWelded StructuresSheet Metal StructuresSpring DesignBolted JointsBearing Arrangement

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL