After energizing, the motor fails to rotate or runs at very low speed with a humming sound; the thermal relay may trip.
① Phase loss (blown fuse / poor contactor contact / broken wire)
② Motor winding ground fault or turn-to-turn short
③ Load mechanically jammed (seized bearing / foreign object blockage)
④ Faulty start capacitor (single-phase motor)
⑤ Supply voltage too low (below 85% of rated)
① Use a multimeter to check three-phase voltage balance (difference ≤10V)
② Disconnect the load and run a no-load start to determine whether the problem is the motor or the load
③ Measure three-phase winding resistance balance (difference ≤2%)
④ Measure insulation resistance (should be >0.5MΩ)
① Inspect the supply circuit (fuse / contactor / thermal relay / wiring)
② If the winding is burned out, send it for repair and rewinding
③ Check the mechanical drive (bearing / coupling / belt)
④ Replace the start capacitor with the same specification
⑤ Install a voltage stabilizer or check the supply wiring
Three-phase current imbalance exceeds 10%; the motor vibrates and overheats, and prolonged operation may burn out the windings.
① Unbalanced three-phase supply voltage
② Motor winding turn-to-turn short
③ Incorrect motor wiring (star connected as delta, or reversed)
④ Poor contactor contact (loose connection on one phase)
① Measure three-phase current with a clamp meter (measure after stopping then restarting)
② Measure and compare the three-phase voltages
③ Measure the DC resistance of each winding phase
① Check whether the three-phase load on the supply network is balanced
② Send for repair and inspect the windings
③ Wire correctly per the nameplate
④ Replace or repair the contactor
A 500V megger shows winding-to-ground insulation <1MΩ, indicating leakage.
① Motor damp (long idle period / ambient humidity >90% / water ingress)
② Dust on winding surface absorbing moisture
③ Insulation aging (exceeded service life / prolonged overheating)
④ Cutting fluid / oil entering the motor terminal box
① Measure insulation resistance (good >5MΩ, caution 1~5MΩ, danger <1MΩ, never operate below <0.5MΩ)
② If possible, measure the absorption ratio (R60/R15 >1.3 indicates good condition)
① Dry the motor (oven at 80℃ for 12h, or low-voltage heating)
② Blow-clean dust from the winding surface
③ Insulation <0.5MΩ requires repair
④ Improve the motor protection rating (e.g., IP54 to IP65)
Operating vibration exceeds ISO 2373; bearing-housing vibration >1.8mm/s.
① Poor rotor dynamic balance (balance weight loosened after long operation)
② Poor motor-to-load alignment (coupling coaxiality >0.1mm)
③ Bearing wear increasing clearance
④ Loose or insufficiently rigid mounting base
⑤ Electromagnetic imbalance (uneven air gap)
① Measure vibration velocity with a vibrometer (normal <1.8mm/s, caution 1.8~4.5, danger >4.5)
② Distinguish bearing vibration from electromagnetic vibration (vibration stops immediately after power-off = electromagnetic issue)
③ Check coupling alignment
① Perform dynamic balancing
② Realign the coupling (laser aligner accuracy 0.01mm)
③ Replace the bearing
④ Reinforce the mounting base
⑤ Replace the worn bearing or adjust the air gap
Metallic friction noise during operation, scrape marks on the stator bore, and smoke in severe cases.
① Severe bearing wear (radial clearance out of tolerance)
② Worn or deformed end-cover register
③ Bent rotor shaft
④ Loose or shifted stator core
① Identify by sound (periodic metallic friction)
② Disassemble and measure the air gap (uniformity deviation >10% is abnormal)
③ Check the bearing radial clearance
① Replace the bearing
② Replace the end cover or repair the register with a sleeve
③ Straighten or replace the rotor shaft
④ Tighten the core clamping bolts
The drive reports an encoder alarm (excessive position deviation / communication error / broken wire) and position control is lost.
① Encoder cable damaged / broken / loose connector
② Encoder contaminated by oil / cutting fluid
③ Encoder subject to strong EMI (routed in the same channel as power cables)
④ Encoder glass code disk cracked by vibration
① Inspect encoder cable appearance and connectors
② Use an oscilloscope to check encoder A/B/Z signal waveforms
③ Substitution method (swap in a known-good encoder to test)
① Replace the encoder cable (must use the original shielded cable, routed separately in a metal conduit)
② Clean the encoder or replace the seal
③ Keep the encoder cable away from power cables (distance ≥300mm)
④ Replace the encoder (requires re-zeroing / homing)
Servo motor brake fails to release or cannot hold; the Z-axis drifts.
① Brake coil burned out (resistance open or shorted)
② Brake rectifier module damaged (no DC output)
③ Brake pad worn beyond limit
④ No brake release signal (relay / PLC output fault)
① Measure brake coil resistance (compare with datasheet)
② Check the brake rectifier input/output
③ Manually release the brake and check pad thickness
① Replace the brake coil or brake assembly
② Replace the rectifier module
③ Replace the brake pads
④ Inspect the brake control circuit (intermediate relay / SSR / PLC output point)
The motor runs with phase loss: speed drops, vibration rises, and current is abnormal.
① Motor cable abraded and broken (drag chain / frequent flexing at moving parts)
② Loose, overheated, or oxidized terminals
③ Power-cable joint pulled apart
① With power off, measure three-phase winding DC resistance
② With power on, measure three-phase current
③ Shake the cable and observe whether the motor jitters
① Replace the entire power cable (joints are failure-prone)
② Re-strip, crimp, and tighten the terminals
③ Check cable protection at moving parts
The thermal relay / motor protector trips and the equipment stops.
① Actual load exceeds motor rated power
② Mechanical drive jamming (bearing / guide / ballscrew issue)
③ Thermal relay setting too low
④ Frequent motor start/stop (more than 6 times per hour)
⑤ Low voltage driving up current
① Use a clamp meter to measure operating current (compare with rated)
② Manually turn the shaft to check mechanical resistance
③ Check the thermal relay setting
① Use a larger motor or reduce the load
② Inspect and repair the mechanical drive
③ Set the thermal relay to the motor rated current (1.0~1.1×)
④ Lengthen run/stop intervals
⑤ Check the supply voltage
Motor temperature rises; the fan does not turn or is noisy.
① Fan blade broken / deformed
② Fan guard clogged (dust / lint)
③ Fan motor burned out (separate fan motor)
④ Air duct blocked
① Check whether the fan turns
② Listen for abnormal fan noise
③ Measure motor surface temperature
① Replace the fan blade
② Clean the fan guard and air duct
③ Repair or replace the fan motor
④ Regularly clean the motor heat-sink fins
During operation the bearing emits metallic friction / irregular / clicking sounds.
① Grease dried out (sharp friction sound)
② Cage damaged (clicking sound)
③ Rolling elements worn or fractured (irregular dull sound)
④ Excessive bearing clearance (humming sound)
⑤ Bearing misaligned during installation
① Use a listening rod / electronic stethoscope to identify the noise type
② Measure vibration
③ Disassemble and inspect the bearing raceway and rolling elements
① Replenish or replace grease (NLGI2 lithium grease, fill 1/3~1/2)
② Replace the bearing
③ Replace the bearing
④ Use a C3-clearance bearing
⑤ Check bearing-housing and end-cover fit
Motor surface temperature exceeds the nameplate allowable rise; too hot to touch and hold.
① Overload (operating current > rated)
② Poor heat dissipation (fan failed / duct blocked / poor ventilation)
③ Ambient temperature too high (>40℃)
④ Voltage too high or too low
⑤ Frequent start/stop or forward/reverse operation
① Measure operating current against rated
② Measure motor surface temperature (Class A ≤80℃, Class E ≤95℃, Class B ≤105℃)
③ Check ventilation and heat dissipation
① Reduce load or use a larger motor
② Clear the duct and repair the fan
③ Improve ventilation or add a forced cooling fan
④ Check the supply voltage
⑤ Reduce start/stop frequency
Motor runs in reverse or the star-delta start sequence is wrong.
① Three-phase supply phase sequence reversed (forward wired as reverse)
② Star-delta start timer delay set incorrectly
③ Star / delta wiring error
① Jog to observe rotation direction
② Check star-delta transition time (typically 5~15s by motor power)
① Swap any two phase wires
② Adjust the star-delta transition time
③ Wire correctly per the nameplate
The VFD reports an overcurrent alarm (OC/SC) and the motor stops.
① Acceleration time set too short
② Motor or cable short / ground fault
③ Motor rated parameters set incorrectly
④ Sudden load change (e.g., mechanical jam)
① Check the VFD fault record code
② Run the motor disconnected at no load to determine whether the fault is the VFD or the motor
③ Check motor insulation
① Extend acceleration time
② Check motor insulation and cable
③ Re-enter the motor nameplate parameters
④ Check the mechanical load
Runs normally unloaded; position drifts once load is applied.
① Motor torque insufficient for the load (torque-speed curve drops)
② Acceleration time too short
③ Driver current setting too low
④ Drive voltage too low
⑤ Load-to-inertia ratio too high
① Run at low speed to check for step loss (more torque available at low speed)
② Measure the driver supply voltage
③ Check the driver current setting
① Lower the operating speed or use a larger motor
② Extend accel/decel time (≥0.3s)
③ Raise the driver current to the motor rated
④ Increase supply voltage (recommend DC36~48V)
⑤ Increase the reduction ratio
During operation the servo drive reports an overload alarm (e.g., AL.051 / Err21).
① Acceleration/deceleration time too short → acceleration torque too high
② Load-to-inertia ratio out of spec → motor must overcome excessive inertia
③ Mechanical jam / stall → load abnormally high
④ Braking resistor undersized → energy cannot be dissipated during deceleration
⑤ Undersized motor → actual torque exceeds rated
⑥ Encoder signal interference → abnormal feedback
① Check the drive alarm code
② Check whether the actual torque monitor value exceeds rated
③ Check whether the inertia-ratio setting is within the recommended range
④ Manually turn the shaft to check mechanical resistance
⑤ Measure the braking resistor resistance
① Extend acceleration/deceleration time
② Increase the reduction ratio to lower the inertia ratio
③ Check mechanical lubrication and assembly
④ Use a larger motor
⑤ Replace the braking resistor
① Metallic friction sound — poor lubrication
② Clicking sound — cage damage
③ Humming sound — insufficient clearance
④ Irregular sound — rolling-element damage
① Replenish grease
② Replace the bearing
③ Select appropriate clearance
④ Check bearing installation
① Acceleration time too short
② Load torque exceeds motor torque
③ Insufficient drive voltage
④ Motor speed near the resonance region
⑤ Inertia ratio too high
① Extend acceleration/deceleration time
② Check the torque-speed curve
③ Raise the driver voltage
④ Avoid the resonance frequency
⑤ Increase the reduction ratio
① Overload (exceeds rated)
② Poor heat dissipation (fan fault / duct blockage)
③ Ambient temperature too high
④ Unbalanced or low voltage
⑤ Frequent start/stop
① Reduce load or use a larger motor
② Clear the duct and check the fan
③ Improve ventilation
④ Check the supply voltage
⑤ Extend run/stop time
Other quick references in this series:Welding defectsHydraulic systemPneumatic systemMotor electricalEquipment faultsStructural part faultsSensor faultsElectrical faultsQuick diagnosisMechanical component faultsBearing faultsGear faultsHydraulic / pneumatic valves