PLC fails to communicate with host computer / touchscreen
① Communication cable broken / connector loose
② Communication parameters mismatch (baud rate / parity / station number)
③ Communication module failure
④ Electromagnetic interference
⑤ Communication distance exceeded
① Check communication indicator lights
② Connect PC directly to PLC to test communication
③ Check communication parameter settings
① Inspect cable and connectors
② Unify communication parameter settings
③ Replace communication module
④ Use shielded twisted pair for communication line and ground it
⑤ Add repeater or switch to RS485 / Ethernet
Touchscreen black screen / white screen / no touch response
① Power supply failure (DC24V output abnormal)
② Backlight damaged
③ Touch panel damaged (cracked screen)
④ Main board failure
⑤ Setting parameters incorrect
① Check power indicator and output voltage
② Check whether screen displays
③ Restart touchscreen
① Repair power supply
② Replace backlight
③ Replace touch panel
④ Replace main board or whole unit
⑤ Reconfigure or restore factory settings
VFD reports OC fault on start or during operation
① Acceleration time too short
② Motor / cable short-circuit or ground fault
③ Motor parameters set incorrectly vs actual
④ Sudden load change (jamming)
⑤ VFD capacity too small
① Check fault code
② Disconnect motor and run unloaded to judge
③ Measure motor insulation
① Extend acceleration time
② Check motor insulation
③ Input motor parameters correctly
④ Inspect load
⑤ Use larger VFD
VFD reports OV fault during deceleration
① Deceleration time too short
② Braking resistor value too high or not connected
③ Load inertia large
④ Grid voltage too high
① Check fault log
② Measure DC bus voltage
③ Check braking resistor wiring
① Extend deceleration time
② Reduce braking resistor or increase power
③ Add braking unit
④ Check grid voltage
Contacts still conduct after relay de-energizes
① Load current too high (exceeds contact rating)
② Inductive load without arc suppression
③ Contact carbon buildup
④ Frequent start/stop
⑤ Spring fatigue
① Power off and measure contact on/off
② Check whether load current exceeds limit
① Derate or use larger contactor
② Add RC snubber circuit or varistor
③ Replace contacts
④ Switch to solid-state relay
⑤ Replace relay
Breaker won't close or trips during operation
① Line short-circuit (neutral-live / phase-to-phase)
② Load too large (exceeds breaker rating)
③ Leakage (residual-current breaker)
④ Breaker itself faulty
⑤ Instantaneous current surge
① Disconnect load and see if it closes
② Use megger to measure line insulation
③ Use clamp meter to measure load current
① Locate and repair short-circuit point
② Reduce load or use larger breaker
③ Check line insulation
④ Replace breaker
⑤ Switch to Type D curve breaker (surge-resistant)
Contactor buzzes after closing
① Iron core mating face has oil / dust
② Short-circuit ring broken
③ Voltage too low, incomplete closing
④ Moving iron core stuck
① Judge by sound (buzzing = core problem)
② Check cleanliness of mating face
③ Measure control voltage
① Clean iron core mating face
② Replace short-circuit ring or contactor
③ Keep voltage at 85~110% of rated
④ Remove stuck object
DC24V power indicator off, no output
① Input power failure (AC220V lost / fuse blown)
② Output overload / short-circuit (protection lockout)
③ Power module damaged
④ Terminal block loose
① Measure whether AC220V is present at input
② Disconnect output load and measure output
③ Check fuse
① Check input power
② Clear output short, power off and restart (supply has auto-recovery)
③ Replace switching power supply
④ Tighten terminals
Multiple sensors lose output simultaneously
① Shared sensor power supply faulty (switching supply failed)
② Power wire broken / fuse blown
③ Supply line short-circuit and tripped
④ Terminal block loose
① Measure supply output voltage
② Check power indicator
③ Measure supply line in sections
① Replace / repair switching supply
② Replace fuse
③ Locate short-circuit point
④ Tighten all terminals
Equipment fails to stop after E-stop pressed, or fails to start after E-stop reset
① E-stop button contacts welded / damaged
② E-stop circuit wiring loose
③ Safety relay fault
④ PLC E-stop input point damaged
⑤ E-stop circuit poorly designed (asymmetric dual-channel)
① Measure E-stop button contact on/off
② Check safety relay status indicator
③ Check PLC E-stop input signal
① Replace E-stop button
② Inspect and tighten wiring
③ Reset or replace safety relay
④ Replace PLC input module
⑤ Rework dual-channel E-stop circuit per safety standard
① Acceleration/deceleration time too short (accel torque exceeds max torque); ② load inertia ratio exceeds recommended value (> 10); ③ mechanical jam (guide / ballscrew stuck); ④ braking resistor capacity insufficient (overvoltage during decel)
① Check drive's actual torque monitor value; ② calculate inertia ratio = load inertia / rotor inertia; ③ disconnect load and turn shaft by hand (high resistance means mechanical jam)
① Extend accel/decel time (at least 0.3~0.5 s); ② increase reduction ratio (lower inertia ratio); ③ check guide / ballscrew lubrication and assembly; ④ increase braking resistor power / resistance
① Encoder cable poor contact (loose plug); ② encoder contaminated by oil / water / dust; ③ encoder internal damage (code disc broken); ④ cable too long, signal attenuation (> 50 m)
① Re-plug encoder connector (confirm locked); ② check encoder-drive communication (oscilloscope waveform); ③ swap encoder to test
① Lock encoder connector / replace cable; ② add encoder protective cover (waterproof / oil-proof); ③ replace encoder or motor; ④ encoder cable length ≤ 50 m (add repeater)
① Accel time too short (start frequency exceeds self-start freq); ② load too large (exceeds motor max torque); ③ driver current set too low; ④ microstep count too high (high-speed torque loss)
① Mark the stop position (check if step loss always occurs at same position); ② measure driver's actual output current; ③ run at lower speed to test
① Extend accel/decel time (trapezoidal profile); ② increase reduction ratio / use larger motor; ③ raise driver current (≤ 1.2× motor rated current); ④ lower microstep count appropriately (≤ 16)
① Phase loss (3-phase motor); ② voltage too low; ③ start capacitor damaged (single-phase motor); ④ rotor stuck / bearing seized
① Measure whether 3-phase voltage balanced; ② turn shaft by hand (check for jam); ③ measure start capacitor capacitance
① Check power cable / contactor / thermal relay (phase-loss protection); ② check supply voltage (±10%); ③ replace start capacitor (capacitance drop); ④ replace motor bearings
① Too much / too little / degraded grease; ② improper bearing clearance (excessive preload); ③ belt too tight (large radial force); ④ poor alignment between motor shaft and driven shaft
① Measure bearing housing temp (IR thermometer); ② listen to bearing sound (hissing / clicking); ③ check belt tension
① Fill appropriate grease (1/3~1/2 of cavity); ② use correct-clearance bearing (C3/CM); ③ adjust belt tension (deflection method); ④ re-align coupling (concentricity ≤ 0.05 mm)
① Motor damp (long idle / humid environment); ② winding end dust buildup (conductive); ③ insulation aging (running > 20 years); ④ water in winding (poor seal)
① Use megger (500 V) to measure ground resistance; ② measure absorption ratio (R60/R15 should be ≥ 1.3)
① Bake dry (80~100°C × 12 h); ② clean winding end dust (vacuum + compressed air); ③ dip in insulating varnish / replace motor; ④ replace seals
① Supply 3-phase voltage imbalance (> 2%); ② motor winding interturn short; ③ poor motor wiring contact (loose terminal); ④ large resistance deviation in one motor phase
① Measure 3-phase supply voltage; ② measure 3-phase winding DC resistance (compare); ③ measure 3-phase current (clamp meter)
① Check supply / transformer 3-phase load balance; ② interturn short needs rewinding / motor replacement; ③ clean and lock terminals; ④ phase resistance deviation > 2% requires motor replacement
① Poor rotor dynamic balance (excess unbalance); ② coupling misalignment; ③ foundation bolts loose; ④ bearing wear; ⑤ electromagnetic vibration (phase loss / interturn short)
① Measure vibration (accelerometer / vibrometer); ② check foundation bolts; ③ run motor uncoupled (judge motor vs load side)
① Balance rotor (grade G2.5); ② re-align (laser aligner / dial indicator); ③ tighten bolts / add shims; ④ replace bearing; ⑤ check supply and windings
① Accel/decel time too short; ② sudden load change (jam / impact); ③ VFD capacity too small; ④ motor insulation damaged (ground short); ⑤ VFD output phase loss
① Check VFD output frequency and current at overcurrent; ② run motor unloaded to test
① Extend accel/decel time (0.5~3 s); ② check mechanical transmission (turns freely?); ③ increase VFD capacity (one size); ④ measure motor insulation resistance; ⑤ check VFD output wiring
① Decel time too short (large regen energy); ② braking resistor not connected / value too high; ③ braking unit damaged; ④ supply voltage too high
① Check braking resistor connection; ② test by extending decel time; ③ measure DC bus voltage
① Extend decel time (critical for high-inertia loads); ② add / replace braking resistor (value per VFD manual); ③ replace braking unit; ④ add input reactor
① Communication cable interfered (shared conduit with power cable); ② comm baud rate mismatch; ③ terminator resistor missing (RS485); ④ comm port hardware damaged
① Check cable routing (away from power lines); ② verify each device's comm parameters; ③ add RS485 end terminator (120 Ω)
① Ground cable shield at single end; ② unify comm parameters (baud / data bits / parity); ③ add signal isolator / repeater; ④ replace comm port / module
① Touchscreen calibration lost (screen replaced); ② touch surface has oil / water stain; ③ touch connection cable loose; ④ touchscreen main board fault
① Recalibrate touchscreen (in system menu); ② clean screen surface; ③ check touchscreen-to-board ribbon connection
① Recalibrate touch (4-point); ② clean screen (neutral cleaner); ③ re-seat touch ribbon; ④ replace touchscreen / main board
① Supply voltage too low (magnetic pull insufficient); ② iron core surface has oil / debris (poor mating); ③ short-circuit ring broken (single-phase hum); ④ contacts burnt / poor contact
① Measure coil voltage (should be 85~110% Us); ② listen (pure hum → short-ring; chatter → low voltage)
① Check supply voltage (add regulator); ② clean core surface (no oil / anticorrosive paint); ③ replace short-ring or contactor; ④ replace contacts / contactor
① Setting current too low (mismatch with motor rated); ② ambient too hot (relay derating); ③ 3-phase imbalance (zero-sequence current trips); ④ wrong relay type (mismatch with motor start profile)
① Verify setting vs motor nameplate; ② measure ambient temp; ③ measure 3-phase current balance
① Re-set current (1.0~1.05× motor rated); ② keep relay away from heat; ③ improve 3-phase balance; ④ use electronic thermal relay for heavy-start motors
① Breaker capacity too small (load grew); ② leakage protection tripped (wiring insulation drop); ③ short-circuit (worn / damp wiring); ④ breaker itself faulty (thermal trip aged)
① Measure actual line current; ② test line insulation; ③ isolate circuits one by one (find which trips)
① Use larger breaker (one size up); ② find leakage point / replace wiring; ③ clear short-circuit; ④ replace breaker
① Load exceeds supply rated power; ② poor cooling (poor ventilation / dust); ③ high ambient temp; ④ switching transistor aged (efficiency drop)
① Measure actual output current (vs rated); ② check mounting (cooling condition); ③ measure input voltage
① Use higher-power supply (margin ≥ 30%); ② improve ventilation (relocate / add fan); ③ lower ambient temp; ④ replace supply
① Contact capacity insufficient (long overload); ② load is inductive (large arc); ③ contact gap carbonized; ④ spring fatigue failure
① Measure contact resistance (should be < 100 mΩ); ② visually inspect contact surface; ③ check release voltage (should be > 10% Us)
① Use one-size-larger relay / contactor; ② add arc-suppression RC or varistor; ③ replace relay; ④ replace spring / relay
① Mounted too close (> 50% of range); ② adjacent sensors interfere; ③ target is ferromagnetic (counts even when close); ④ power interference (high ripple)
① Measure actual mounting distance; ② remove target and check reset; ③ scope power ripple
① Adjust mounting distance (keep safe distance); ② spacing ≥ 3× detection diameter; ③ use shielded sensor; ④ add filter / separate supply
① Response time longer than object transit time; ② object transparent / translucent (diffuse type); ③ lens dust / contamination; ④ one end of through-beam offset
① Calculate transit time (speed × detection width); ② check lens cleanliness; ③ check through-beam alignment
① Use faster photoelectric switch (0.5 ms); ② use through-beam or fiber for transparent objects; ③ clean lens (lens cloth + alcohol); ④ re-align emitter/receiver
① Zero offset after long use; ② mounting stress (over-torque); ③ diaphragm deformed (overload); ④ temperature change (thermal zero drift)
① Remove sensor (measure output at zero pressure); ② check torque (per manual); ③ zero-calibrate (electrical)
① Electrical zero (zero pot to 0 output); ② install with torque wrench; ③ replace sensor (overload damage); ④ use low-drift sensor (±0.02%/°C)
① Large package thermal mass (long response); ② poor mounting (sheath-medium contact poor); ③ probe fouling / coking
① Check datasheet (response time τ); ② check insertion depth (to medium center)
① Use faster sensor (thermocouple < RTD < thermistor); ② add thermal grease (probe-sheath); ③ clean probe surface; ④ deeper install (≥ 1/3 pipe dia)
① Sensor tilted (cosine error); ② detection surface uneven / not perpendicular; ③ poor linearity (range exceeds rated stroke); ④ large ambient temperature change
① Calibrate vs gauge block / micrometer; ② check mounting angle
① Adjust mounting (axis ∥ motion); ② add bracket / adjust surface; ③ stay within rated range; ④ add temp compensation / low-drift sensor
① Coupling misalignment (adds bending moment); ② unstable supply (high ripple); ③ used beyond range (nonlinear); ④ strong magnetic interference nearby (VFD / motor)
① Check zero drift unloaded; ② scope power ripple; ③ check range utilization
① Re-align coupling (concentricity ≤ 0.05 mm); ② add regulated supply / filter; ③ stay within range (20% margin); ④ shield sensor / keep from VFD
① Elastic element material creep (stress relief); ② overload (plastic deformation); ③ unstable base (deformation); ④ junction box damp (resistance change)
① Record 60-min output under constant load; ② inspect appearance (deformation); ③ measure bridge resistance
① Replace sensor (creep irreversible); ② confirm load within range (incl. shock); ③ reinforce base (rigid); ④ dry junction box / add sealant
① Sensor position shifted; ② sensor faulty / aged; ③ reflector moved / dirty; ④ safety relay fault
① Manually block beam to test; ② check safety relay status; ③ check reflector position
① Recalibrate sensor position; ② replace sensor (safety category III); ③ fix / clean reflector; ④ replace safety relay; ⑤ periodic functional test (daily)
① Misalignment (emitter/receiver offset); ② curtain surface contaminated; ③ sync line / cable loose; ④ controller fault
① Check emitter/receiver indicators; ② block each beam (find which fails); ③ check wiring
① Re-align (emitter green); ② clean protection window (lens cloth); ③ lock cable connectors; ④ replace controller / curtain
① Wrong sensor choice (ultrasonic has blind zone); ② low frequency (large blind zone); ③ mounted too close to target
① Check datasheet (blind zone); ② adjust mounting distance (increase)
① Use higher-frequency ultrasonic (higher freq → smaller blind zone); ② keep distance > blind zone; ③ if unavoidable, mount at angle
① Insufficient color contrast (ΔE < 10%); ② improper detection distance; ③ wrong light color (white / RGB choice); ④ ambient light interference (sunlight / lighting)
① Use built-in teach function; ② tune detection distance to best (lamp on); ③ compare signal strength under light colors
① Increase mark-background contrast (high-contrast color); ② precisely tune distance (max signal); ③ choose matching light color; ④ add light shield
① Fiber head contaminated / damaged (end worn); ② distance too far (beyond amplifier); ③ head not perpendicular to target; ④ sensitivity set too low
① Clean fiber end (anhydrous alcohol); ② check amplifier margin (should be ≥ 2×); ③ check head angle
① Replace head / cut front end (remove contaminated part); ② shorten distance; ③ adjust head (perpendicular); ④ raise amplifier sensitivity / threshold