Common Faults · Sensor Faults (Quick Reference)

Photoelectric Sensor Unstable Detection Analysis and Remedy

【Symptom】

With a workpiece present, the sensor sometimes detects it and sometimes does not

【Possible Causes】

① Detection distance too short or too long (outside the effective range)

② Workpiece surface reflective / transparent / black and light-absorbing

③ Dust on the lens

④ Through-beam sensor not properly aligned

⑤ Ambient light interference (sunlight / welding arc)

【Diagnostic Methods】

① Test with a test piece at multiple positions

② Check the blinking pattern of the sensor indicator

③ Check the cleanliness of the lens

【Remedies】

① Adjust the mounting distance within the effective detection range

② Use fiber-optic or ultrasonic sensors for transparent / black workpieces

③ Clean the lens (with lens tissue)

④ Re-align

⑤ Add a light shield

Proximity Sensor False Triggering Analysis and Remedy

【Symptom】

The sensor has an output when there is no target present

【Possible Causes】

① Mounting distance too short (more than 50% of the detection distance)

② Mutual interference between adjacent sensors

③ Ferromagnetic target causing false sensing

④ Power supply interference

【Diagnostic Methods】

① Measure the actual distance between the sensor and the target

② Remove the target and check whether the output resets

【Remedies】

① Adjust the mounting distance

② Space the sensors at ≥3 times the detection distance

③ Use shielded sensors

④ Add a power line filter

Pressure Sensor Zero Drift Analysis and Remedy

【Symptom】

The sensor output is not zero when there is no pressure

【Possible Causes】

① Sensor diaphragm deformed or damaged (overload)

② Large ambient temperature changes (thermal drift)

③ Excessive mounting torque deforming the housing

④ Sensor aging

【Diagnostic Methods】

① Disconnect the pressure port and measure the zero output

② Compare the zero point with a normal sensor of the same model

【Remedies】

① Recalibrate the zero point

② Pressure sensors are subject to thermal drift; calibrate only after the ambient temperature is stable

③ Install at the specified torque

④ Replace the sensor

Slow Response of the Temperature Sensor Analysis and Remedy

【Symptom】

The actual temperature has already changed but the sensor reading lags behind

【Possible Causes】

① Poor contact between the probe and the measurement point

② Probe protection tube too thick

③ Insufficient probe insertion depth

④ Dirt deposit on the probe surface

【Diagnostic Methods】

① Check the contact between the probe and the measured part

② Compare with the reading of another thermometer

③ Check the insertion depth

【Remedies】

① Improve the contact (apply thermal grease / press firmly)

② Fit a thin-wall protection tube

③ Ensure the insertion depth is ≥10 times the protection tube diameter

④ Clean the probe

Displacement Sensor Out-of-Tolerance Analysis and Remedy

【Symptom】

Large deviation between the measured value and the actual value

【Possible Causes】

① Loose mounting / displacement

② Sensor range does not match the measurement range

③ Large linearity error

④ Electromagnetic interference

【Diagnostic Methods】

① Compare and calibrate against a standard gauge such as a dial indicator

② Check the mounting and fixing condition

【Remedies】

① Re-fix the sensor

② Select a sensor with a close range (operate at 20~80% of range)

③ Calibrate at regular intervals

④ Use shielded twisted-pair cable

Encoder Pulse Loss Analysis and Remedy

【Symptom】

The position count does not match the actual position

【Possible Causes】

① Encoder coupling to the shaft is loose

② Encoder cable is disturbed (routed in the same tray as the power cables)

③ Encoder frequency exceeds the limit

④ Receiving module response speed insufficient

【Diagnostic Methods】

① View the encoder waveform on an oscilloscope

② Count at low speed to check whether the count is accurate

【Remedies】

① Tighten the coupling

② Route the encoder cable separately in shielded metal conduit

③ Reduce the speed or select a high-frequency encoder

④ Fit a high-speed counter module

Force Sensor Overload Damage Analysis and Remedy

【Symptom】

The sensor output does not change, or it stays at full scale

【Possible Causes】

① Applied force exceeds the sensor rated capacity

② Shock load (drop / impact)

③ Improper sensor mounting (side load / bending moment)

④ Incorrect wiring causing an unbalanced bridge circuit

【Diagnostic Methods】

① Measure the sensor output (zero + full scale)

② Inspect the sensor exterior for deformation or cracks

③ Measure whether the bridge resistance is balanced

【Remedies】

① Replace the sensor

② Add mechanical stops / shock protection

③ Select a sensor one size larger in range

④ Wire correctly according to the manual

Vision Sensor Poor Detection Analysis and Remedy

【Symptom】

The camera cannot identify the workpiece or misjudges it

【Possible Causes】

① Unsuitable light source brightness / angle

② Lens focus not properly adjusted (blurred image)

③ Workpiece position outside the field of view

④ Program template does not match the current workpiece

⑤ Ambient light changes

【Diagnostic Methods】

① Check whether the camera image is clear

② Check whether the light source is working normally

③ Check the workpiece position

【Remedies】

① Adjust the light source (ring light / back light / coaxial light)

② Adjust the lens focus and aperture

③ Adjust the workpiece locating or the camera position

④ Re-create the template

⑤ Add a light shield against ambient light

Ultrasonic Sensor Blind Zone Analysis and Remedy

【Symptom】

Objects cannot be detected at close range

【Possible Causes】

① Intrinsic blind zone of the sensor (transducer ring-down)

② Installed too close to the workpiece

③ Target absorbs sound (porous material / soft fabric)

【Diagnostic Methods】

① Check the blind zone distance in the sensor specification

② Test with a hard flat surface at several distances

【Remedies】

① Keep the sensor farther from the workpiece than the blind zone (generally 30~100mm)

② Mount at an angle so the sound wave reflects

③ Use a photoelectric sensor for sound-absorbing materials

Insufficient Light Level in the Fiber Optic Sensor Analysis and Remedy

【Symptom】

The amplifier indicates insufficient light and the detection is unstable

【Possible Causes】

① Contaminated or worn fiber end face

② Fiber bending radius too small (high optical loss)

③ Fiber length too long

④ Fiber head loose on the amplifier connector

【Diagnostic Methods】

① Check the light level displayed on the amplifier

② Clean the fiber end face

③ Check the fiber bend condition

【Remedies】

① Clean or cleave the fiber end face (with a dedicated cleaver)

② Bending radius ≥25mm

③ Shorten the fiber or use a large core diameter fiber

④ Re-seat the connector firmly