With a workpiece present, the sensor sometimes detects it and sometimes does not
① Detection distance too short or too long (outside the effective range)
② Workpiece surface reflective / transparent / black and light-absorbing
③ Dust on the lens
④ Through-beam sensor not properly aligned
⑤ Ambient light interference (sunlight / welding arc)
① Test with a test piece at multiple positions
② Check the blinking pattern of the sensor indicator
③ Check the cleanliness of the lens
① Adjust the mounting distance within the effective detection range
② Use fiber-optic or ultrasonic sensors for transparent / black workpieces
③ Clean the lens (with lens tissue)
④ Re-align
⑤ Add a light shield
The sensor has an output when there is no target present
① Mounting distance too short (more than 50% of the detection distance)
② Mutual interference between adjacent sensors
③ Ferromagnetic target causing false sensing
④ Power supply interference
① Measure the actual distance between the sensor and the target
② Remove the target and check whether the output resets
① Adjust the mounting distance
② Space the sensors at ≥3 times the detection distance
③ Use shielded sensors
④ Add a power line filter
The sensor output is not zero when there is no pressure
① Sensor diaphragm deformed or damaged (overload)
② Large ambient temperature changes (thermal drift)
③ Excessive mounting torque deforming the housing
④ Sensor aging
① Disconnect the pressure port and measure the zero output
② Compare the zero point with a normal sensor of the same model
① Recalibrate the zero point
② Pressure sensors are subject to thermal drift; calibrate only after the ambient temperature is stable
③ Install at the specified torque
④ Replace the sensor
The actual temperature has already changed but the sensor reading lags behind
① Poor contact between the probe and the measurement point
② Probe protection tube too thick
③ Insufficient probe insertion depth
④ Dirt deposit on the probe surface
① Check the contact between the probe and the measured part
② Compare with the reading of another thermometer
③ Check the insertion depth
① Improve the contact (apply thermal grease / press firmly)
② Fit a thin-wall protection tube
③ Ensure the insertion depth is ≥10 times the protection tube diameter
④ Clean the probe
Large deviation between the measured value and the actual value
① Loose mounting / displacement
② Sensor range does not match the measurement range
③ Large linearity error
④ Electromagnetic interference
① Compare and calibrate against a standard gauge such as a dial indicator
② Check the mounting and fixing condition
① Re-fix the sensor
② Select a sensor with a close range (operate at 20~80% of range)
③ Calibrate at regular intervals
④ Use shielded twisted-pair cable
The position count does not match the actual position
① Encoder coupling to the shaft is loose
② Encoder cable is disturbed (routed in the same tray as the power cables)
③ Encoder frequency exceeds the limit
④ Receiving module response speed insufficient
① View the encoder waveform on an oscilloscope
② Count at low speed to check whether the count is accurate
① Tighten the coupling
② Route the encoder cable separately in shielded metal conduit
③ Reduce the speed or select a high-frequency encoder
④ Fit a high-speed counter module
The sensor output does not change, or it stays at full scale
① Applied force exceeds the sensor rated capacity
② Shock load (drop / impact)
③ Improper sensor mounting (side load / bending moment)
④ Incorrect wiring causing an unbalanced bridge circuit
① Measure the sensor output (zero + full scale)
② Inspect the sensor exterior for deformation or cracks
③ Measure whether the bridge resistance is balanced
① Replace the sensor
② Add mechanical stops / shock protection
③ Select a sensor one size larger in range
④ Wire correctly according to the manual
The camera cannot identify the workpiece or misjudges it
① Unsuitable light source brightness / angle
② Lens focus not properly adjusted (blurred image)
③ Workpiece position outside the field of view
④ Program template does not match the current workpiece
⑤ Ambient light changes
① Check whether the camera image is clear
② Check whether the light source is working normally
③ Check the workpiece position
① Adjust the light source (ring light / back light / coaxial light)
② Adjust the lens focus and aperture
③ Adjust the workpiece locating or the camera position
④ Re-create the template
⑤ Add a light shield against ambient light
Objects cannot be detected at close range
① Intrinsic blind zone of the sensor (transducer ring-down)
② Installed too close to the workpiece
③ Target absorbs sound (porous material / soft fabric)
① Check the blind zone distance in the sensor specification
② Test with a hard flat surface at several distances
① Keep the sensor farther from the workpiece than the blind zone (generally 30~100mm)
② Mount at an angle so the sound wave reflects
③ Use a photoelectric sensor for sound-absorbing materials
The amplifier indicates insufficient light and the detection is unstable
① Contaminated or worn fiber end face
② Fiber bending radius too small (high optical loss)
③ Fiber length too long
④ Fiber head loose on the amplifier connector
① Check the light level displayed on the amplifier
② Clean the fiber end face
③ Check the fiber bend condition
① Clean or cleave the fiber end face (with a dedicated cleaver)
② Bending radius ≥25mm
③ Shorten the fiber or use a large core diameter fiber
④ Re-seat the connector firmly