In a jog loop the fuse handles short-circuit and big overload by melting instantly, while the thermal relay handles sustained overload with a bimetal strip and inverse-time action. This page shows how they share the job and how to set each rating.
Fuse FU only protects against short circuit and very large overload, melting fast but blind to small overload; thermal relay FR protects long overload, its bimetal bends to open a contact in series with the contactor coil so the motor stops. They do not overlap: short circuit by FU, overload by FR, miss one and you leave a gap.
Set FR rated current near motor rated current, about 0.95 to 1.05 times, or 1.1 to 1.2 times for frequent jog loads like cranes to avoid nuisance trip, never above motor allowed overload. Fuse rating is 2 to 3.5 times motor current to ride through start surge yet still clear a fault. Too small a fuse blows on every jog start; too large never clears a short. The coil circuit gets its own 2 to 6 ampere small fuse.
| Protect | For | Set |
|---|---|---|
| Fuse FU | short | 2-3.5x Ie |
| Thermal FR | overload | 0.95-1.05 Ie |
| FR contact | cut control | in KM coil |
| Coil fuse | ctrl short | 2-6 A |
| Crane jog | frequent | FR 1.1-1.2 |
| Forbid | wire for fuse | danger |
Keep the protection split clear: short circuit to the fuse, overload to the thermal relay, each set by its own factor, with the thermal relay slightly relaxed for frequent jog loads. Never replace a fuse link with wire; if the relay nuisance-trips, switch to a temperature-compensated model and manual reset.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage fuses follow GB/T 13539 with IEC 60269; thermal relays fall under GB/T 14048 with IEC 60947. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.