Long multi-point runs sit near power and, with poor earthing or shielding, the contactor chatters intermittently for months untraced. This note covers the earthing method, shield handling and equipotential bonding so the system stays quiet.
Control circuits are usually floating or high-resistance earthed, never grounded at many points. If several button boxes each earth locally, the potential difference drives a circulating current in the shield or between wires, injecting noise or even burning parts. The rule is single-point earthing: the control reference ties to protective earth at one point only inside the cabinet; remote boxes may earth their shield and metal case but not the signal return. GB/T 5226.1 and GB/T 16895 state this clearly.
A shielded control cable must have its shield earthed at one end only, at the cabinet or receiver side, the far end floating. Both ends earthed makes a loop driven by ground-potential difference that couples power noise into the signal, worse than no shield. Armour or conduit is earthed the same single way with at least 2.5 sq mm copper to the cabinet bus. Bond all box cases, brackets and trays for equipotential; separate control from power, vertical crossing near drives; measure potential difference and loop current before energising.
| Item | Do | Wrong | Basis |
|---|---|---|---|
| Circuit earth | One point | Many points | GB/T 5226.1 |
| Shield | One end | Both ends | GB/T 16895 |
| Metal case | Equipotential | Floating | Shock |
| Routing | Separate | Same tray | GB 50217 |
| Earth wire | >=2.5 sq | Thin loose | Bus |
| Accept | Measure | Skip | Sign |
Earthing and shielding are the foundation of immunity. Single-point earth, one-end shield, case equipotential and separation from power are four iron rules. When chatter appears, first measure the voltage difference between earth points and check for double-ended shield, which cause over eighty percent of noise faults.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Earthing and equipotential per GB/T 16895 and GB/T 5226.1, routing per GB 50217. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.