Missing symbols and duplicated designations are common basic errors, and review must hunt them specifically. This page explains the checking methods and the tools for both.
Missing symbols come in two kinds: the hardware exists but no symbol was drawn, for example a thermal relay fitted but its contact omitted; and a symbol exists but carries no letter code, so it cannot be identified. The method: walk the material list or device list against the drawing, confirming every device has its symbol and code; then sweep circuit by circuit, checking that every motor, breaker, contactor and thermal relay in the main circuit appears. Software can compare the device list against the drawn symbols and flag the gaps automatically.
Duplicate designation means one device labelled with two different codes, or one code used twice for different devices. The check: tally every letter code across the drawing and confirm each maps to exactly one device; all contacts and coils of one KM must belong to the same contactor, and two unrelated KM1 tags are a conflict. Software uniqueness validation flags duplicates in red; manual checking sorts the codes alphabetically and walks them one by one.
| Check item | Method | Tool | Key point |
|---|---|---|---|
| Missing device | list walked against drawing | BOM comparison | every item has a symbol |
| Missing code | symbol checked for its code | visual | code always present |
| Duplicate code | uniqueness validation | software | one code one device |
| List versus drawing | two-way check | two people | kept in step |
| Cross check | another reader reviews | manual | beats familiarity blindness |
Hunt missing symbols by walking the device list against the drawing so every device owns a symbol and a code, and hunt duplicates by validating code uniqueness so one code maps to one device. Self-review misses what familiarity hides, so cross-check with a second reader; run the software BOM comparison and uniqueness validation first and follow with a manual logic pass, keeping the material list and the drawing in step.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Checking per the review requirements of GB/T 6988 and the annotation rules of GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.