Self-hold (run) means press start once, release the button and the motor keeps running, held by the contactor holding itself. This page explains how the latch works and what the latch contact does.
The latch circuit parallels a normally open auxiliary contact KM of the contactor across the start button SB2. Start: press SB2, control path L to SB2 to KM coil to N closes, KM pulls in and feeds the motor; at the same time the KM NO auxiliary closes. After releasing SB2 the current reroutes through the KM auxiliary branch to keep the coil fed, so the motor keeps running. That is the contactor holding itself, self-hold.
The latch contact (KM NO auxiliary) is the key to keep running: it bypasses the start button so the coil stays fed after the button is released. Without it, release stops (that is jog). So the latch contact must come from the same contactor, rating 5 to 10 A is enough because it only carries control current. It is linked to the main contact: when main pulls in, aux closes; when main releases, aux opens. Stop button SB1 is NC in series; pressing cuts the whole control loop including the latch branch, KM drops, motor stops, and a fresh start is needed.
| Part | Role | Wire |
|---|---|---|
| Start SB2 | trigger | NO |
| KM aux | self-hold | par SB2 |
| Stop SB1 | cut ctrl | NC ser |
| Coil | energized | via contact |
| Main | feed motor | linked |
| Thermal | overload | NC ser |
The latch parallels the contactor NO auxiliary across the start button; after release the aux keeps the coil fed for run. The latch contact comes from the same KM, 5 to 10 A, linked to the main contact. Stop is a NC button cutting the control loop, with thermal overload; miss either and it is unsafe.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage devices per GB/T 14048 with IEC 60947, safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.