Undersized low-voltage apparatus burns, oversized is costly and protects poorly, so selection must follow rules. This article explains the general principles and verification for selecting circuit breakers, contactors, relays and fuses in control circuits.

1. How it works

First select by rated parameters: rated voltage not below system voltage, rated current not below load current, same frequency. Breakers are chosen by breaking capacity against prospective short-circuit current, contactors by AC-3 or AC-4 category and motor power, relays by coil voltage and controlled object. Also consider mounting, enclosure rating, ambient temperature and altitude derating. Match frame size and pole count to the main circuit and fit accessories as needed.

2. Practice and pitfalls

Select by utilisation category and life: motor contactors use AC-3 for normal start-run or AC-4 for frequent reversing, with AC-4 electrical life much shorter so derate. Breakers use C or D curve for motor starting to avoid nuisance trip, not B. Estimate electrical life and operating frequency, and upsize for frequent duty. Always check rated, breaking, category, life and derating five items, leave margin on critical circuits and achieve selective coordination.

3. Apparatus Selection Rules Table

ItemRuleCheck
Voltage>= systemNameplate
Current>= loadDerate
Breaking>= faultSystem
CategoryAC-3/AC-4Load
LifeMatch freqUpsize

4. Notes

General selection rules cover five items: rated voltage, current, breaking capacity, utilisation category and life with derating. Never skip breaking capacity, never use AC-3 for AC-4 duty, and choose C or D curve for motors. Leave margin per load characteristic.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear see GB/T 14048 series (GB/T 14048.5 contactor, GB/T 14048.2 breaker), electrical safety see GB/T 5226.1 (IEC 60204-1). Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Current only no breaking: breaker bursts on fault
② AC-3 used as AC-4: life drops fast
③ B curve on motor: trips at start

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.